22
947180
6 6 SET ZONE OR GROUP ZONE TO REMOTE MONITOR
This option selects a zone or group zone for computer monitoring, (logging of paging activity), or for
visual message display. The default setting is off (Refer to Step 10).
1. Dial
6 6
to select this option.
Hear a DOUBLE beep.
2. Enter zone or group zone number.
3. Dial the code to activate this option:
0
to select OFF
1
to select ON.
Hear TRIPLE beeps.
4. To verify the status of this option, dial
6 7
and repeat step 2 above.
OUTPUT ZONE/GROUP CONFIGURATIONS
These options apply to zones or groups already configured as outputs (see Step 17, Type of Zone). All
these parameters can be individually optioned per zone. For a summary of these options, see the Pro-
gramming Quick Reference Chart at the end of this section.
7 0 SET OUTPUT ZONE TYPE
This option selects the type of output for an individual output zone. The choices here are Audio/Normally
Open, Normally Closed, System Handshake, Momentary Open, Toggle, Phantom, and Attendant Access
Handshake. The Audio/Normally Open option is the default. The primary use for the Normally Closed Or
System Handshake is to determine how the switch closure is to function.
When the System Handshake option is chosen, the closure will energize when a valid Off Hook condition
has been detected. The Attendant Access Handshake zone provides an output contact closure when
Attendant Access interface is ready to make a page.
Note:
System Handshake is a feature required by certain PBX systems: when they access the paging
system, they require a return acknowledgment signal – the “handshake” – from the Controller.
A Phantom Zone is an output zone that exists only in software. If a page is made to a Phantom zone, the
controller will send a message to an attached monitoring device (if configured) and will issue confirma-
tion tone, but will take no action with respect to the zone's hardware. This allows uninstalled zones to be
used to select messages on a visual display.
The Momentary Open, Normally Closed and Toggle options are intended to be used for controlling door
striker plates, for instance, to permit a security door to be unlocked. The Momentary Open will stay ener-
gized for as long as the zone is selected. The Toggle will stay energized for as long as the zone is
selected. Normally Closed will open only when the specific zone is selected. Neither of these modes will
respond to an Attendant Access page, an All-Call and/or Zone Grouping page.
Repeat this procedure for each output zone.
1. Dial 7 0 to select this option.
Hear a DOUBLE beep.