Filtering
1282
0501
hex
Enable of disable
measurement filtering using
the user-defined filtering
factor (register 031A
hex
)
16-bit boolean
0 = Off
1 = On
Communication
1537
0600
hex
Modbus address
16-bit integer
1 ... 247
Default: 240
1538
0601
hex
Bit rate
enum
0 = 300
1 = 600
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 19200
7 = 38400
8 = 57600
9 = 115200
1539
0602
hex
Parity, data, stop bits
enum
0 = None, 8, 1
1 = None, 8, 2
2 = Even, 8, 1
3 = Even, 8, 2
4 = Odd, 8, 1
5 = Odd, 8, 2
(default: 1 = None, 8, 2)
1540
0603
hex
Response delay
16-bit integer
Unit: ms
Range: 0 ... 1000
Functions
1285
0504
hex
Start purge
16-bit function
status
When writing to
register:
1 = Start purge
1542
0605
hex
Restart device
16-bit function
status
When writing to
register:
1 = Restart the device
HMP Series with MMP8 and TMP1 User Guide
M212022EN-F
106