USER'S GUIDE____________________________________________________________________
118 _________________________________________________________________ M210704EN-F
INTV
Use the
INTV
command to set the RUN mode output interval. The time
interval is used only when the RUN mode is active.
INTV
[
xxx yyy
]<cr>
where
xxx
= Delay, range 1 – 255.
yyy
= Unit: S, MIN or H.
Example (setting the output interval to 10 minutes):
>
intv 10 min
Output interval: 10 min
>
Setting RUN output interval to zero enables the fastest possible output
rate.
SDELAY
With the
SDELAY
command you can set delay (response time) for user
port, or view currently set delay value. Adjusting the delay may be
needed when half-duplex communication (typically two-wire RS-485) is
used.
The delay value corresponds to tens of milliseconds (for example, 5 =
0.050s minimum answer delay). The value can be set between 0 ... 254.
Example:
>
sdelay
Serial delay : 0 ?
10
>
sdelay
Serial delay : 10 ?