57
Installation Instructions VRC 630 0020095108_00
Operating the controller 7
7.3
Setting and optimising parameters in the
Installer level
The system parameters are set in the Installer level. You
can also call up various system values here. The Instal-
ler level is protected against unauthorised access by an
access code and is enabled for 60 minutes after the
code has been entered correctly.
You can access the Installer level by turning the left
hand knob until Menu
C1
is reached.
Enter the access code which will allow the system-
specific parameters to be altered in future.
If you do not enter any access code, the parameters in
the subsequent menus are displayed after pressing the
knob once, but cannot be changed.
The default access code is 1 0 0 0. You can change the
code in Menu
C1
.
The Installer level is operated in the same way as the
Operator level. The parameters are selected likewise by
turning and pressing the knob. All the accessible
menus and their parameters can be found in the appen-
dix in the tables "Settings in the Installer level" and
"Settings in the Installation Assistant".
Furthermore you can check that all the sensors, pumps
and mixers are working properly using the manual mode
in the Installer level.
All menus which can be accessed in the Installer level,
together with the parameters and displayed values, are
listed in the following tables.
>
Summary of Contents for VRC 630
Page 1: ...GB VRC 630 3 ...
Page 2: ......
Page 54: ......
Page 55: ...For the heating engineer Installation Manual VRC 630 ...
Page 152: ...0020095108_00 GB 022010 Subject to alterations ...