21
Installation Manual auroMATIC 560 0020060907_00
GB
Display
Setting by turning the dial
Setting range
Default setting
Set the activation difference for Cylinder 1
(The activation difference should always be
2 K greater than the deactivation difference)
2 - 25 K
7 K
Set the deactivation difference for Cylinder 1
(The deactivation difference should always be
2 K less than the activation difference)
1 - 20 K
3 K
Set the maximum temperature for Cylinder 2
20 - 90 °C
60 °C
Table 6.1 System parameters (continuation)
a
Caution:
The maximum permissible temperature for the
installed cylinder (MAXT 2) must not be ex-
ceeded.
Display
Setting by turning the dial
Setting range
Default setting
Set the activation difference for Cylinder 2
(The activation difference should always be
2 K greater than the deactivation difference)
2 - 25 K
7 K
Set the deactivation difference for Cylinder 2
(The deactivation difference should always be
2 K less than the activation difference)
1 - 20 K
3 K
PRIO
Cylinder with highest priority
1, 2
1
FROS:
Frost protection function
-5 °C – 10 °C; OFF
OFF
Table 6.1 System parameters (continuation)
Start-up 6