61
Installation instructions geoTHERM VWS/VWW 0020057444_01
Display shown
Description
Factory setting
Menu A: Installation Assistant
You will be guided through the Installation Assistant,
Menus A1 and A2, during the initial commissioning of
the heat pump.
The Installation Assistant appears automatically dur-
ing initial commissioning.
Installation
A1
Language selection
Language
>GB english
>Select
Language
: Set the local language
During the initial installation the controller always
starts with this menu (Installation Assistant).
Installation assistant
A2
Hydraulic scheme
3
Heat pump type
5
Electroplan
1
Accept change
Yes
>Select
The hydraulic and electro plans must be set by the
installer during initial commissioning.
The heat pump type has already been set at the fac-
tory and may not be changed!
Hydraulic plan:
1 = no buffer cylinder, no DHW cylinder
2 = with buffer cylinder, no DHW cylinder
3 = no buffer cylinder, with DHW cylinder
4 = with buffer cylinder, with DHW cylinder
See Figs. 6.8 to 6.11.
Note
: Other hydraulic plans may only be set if the
VWZ NC 14/17 accessory is used. More detailed infor-
mation regarding this can be found in the installa-
tion manual for the VWZ NC 14/17 accessory.
Heat pump type:
Type Description
4
VWS
61/2
6
VWS
81/2
8
VWS
101/2
9
VWS
141/2
10
VWS
171/2
16
VWW
61/2
18
VWW
81/2
20
VWW
101/2
21
VWW
141/2
22
VWW
171/2
Electroplan:
1 = all on the high tariff (see Fig. 6.2).
2 = low tariff for the compressor (see Fig. 6.3).
3 = low tariff for the compressor and electric auxilia-
ry heating (see Fig. 6.4).
Accept change:
Yes/No;
"Yes" means that all the set values will be saved.
Table 8.4 Parameters that can be set in the Code level (cont.)
Controller 8