Installation instructions geoTHERM VWS/VWW 0020057444_01
34
6.7.4 Direct heating operation and domestic hot
water cylinder (Hydraulic plan 3)
The heat pump is connected directly to the underfloor
heating circuit. Control system is carried out using ener-
gy balance control by default (see Chap. 8.4.2). The VF2
flow temperature sensor must be connected (floor pro-
tection circuit).
The heat pump also supplies a domestic hot water cylin-
der.
SP
42b
32
33
WQ
16
VF2
30
31
30
31
42a
400 V
400 V
43
25
KW
AF
VF2
30
31
39
27
Fig. 6.10 Hydraulic plan 3
Key to Fig. 6.10
16
External sensor (AF)
25 Circulation
pump
30 Non-return
valve
31
Control valve with position indication
32 Cap
valve
33
Air separator/Dirt filter
42a Expansion
relief
valve
42b Expansion
vessel
43
Safety group for hot water pipe
VF2 Supply temperature sensor
SP
Cylinder temperature sensor
WQ
Heat source circuit
KW
Cold water
optional for hydraulic decoupling:
27
Heating circuit pump with control line to the heat pump
39
Low loss header
h
Note!
Should hydraulic decoupling of the heat-
ing circuit be necessary, then fit a low
loss header and an external heating cir-
cuit pump as shown in Fig. 6.10.
h
Note!
If you have fitted a low loss header be-
tween the heat pump and the heating
system, then the VF2 temperature sen-
sor must be mounted in the flow line
from the low loss header to the heating
system.
6 Electrical installation