35
Installation instructions geoTHERM VWS/VWW 0020057444_01
6.7.5 Mixer circuit with buffer cylinder and
domestic hot water cylinder
(Hydraulic plan 4)
The unregulated underfloor heating circuits are operat-
ed by the external heating circuit pump from the buffer
cylinder via a mixer. The flow temperature sensor sits
behind the external pump.
The heat pump responds to a demand for heat from the
buffer cylinder.
SP
42a
AF
43
25
KW
42b
32
VF1
46
VF2
27
RF1
55
30
31
30
30
31
M
WQ
33
400 V
400 V
Fig. 6.11 Hydraulic plan 4
Key to Fig. 6.11
16
External sensor (AF)
25 Circulation
pump
27 CH
pump
30 Non-return
valve
31
Control valve with position indication
32 Cap
valve
33
Air separator/Dirt filter
42a
Expansion relief valve
42b Expansion
vessel
43
Safety group for hot water pipe
46
3-way mixer valve
VF1
Buffer cylinder head temperature sensor
VF2
Supply temperature sensor
RF1
Buffer cylinder base temperature sensor
SP
Cylinder temperature sensor
WQ
Heat source circuit
KW Cold
water
Electrical installation 6