VAG Operation and Maintenance Instructions • 7

Permissible

Impermissible

Upright           

installation 

position

Picture 10: Installation position of the Automatic Air Valve

90°

<> 90°

4.4.1  Installation position downstream from  

 pumps

If the VAG DUOJET

®

 Automatic Air Valve has to be installed 

downstream from pumping stations, positioning must take place 

according to the “ideal” installation position shown in Picture 11.

Picture 11: Installation position downstream from pumps

Impermissible     

installation position

Ideal installa-

tion position

4.4.2  Installation in standpipes

Standpipes result in high flow velocities during the filling process. 

If the VAG DUOJET

®

 Automatic Air Valve is installed directly on 

the standpipe there is a risk of the ball closing prematurely.

To prevent premature closing we recommend the installation of a 

multiple-orifice plate in front of the valve (cf. Picture 12).

4.4.3  Discharging splashing or surge water

When intentionally discharging splashing or surge water via the 

pipeline it should be cut off slowly  downstream of the valve so 

that no improper suction effect impacts the VAG DUOJET

®

 Auto-

matic Air Valve (cf. Picture 13).

Picture 12: Installation position in standpipe

Impermissible ins-

tallation position

(risk of suction effect)

Ideal installation position

(elbow and down-pipe separated)

Picture 13: Installation position for splashing or surge water

Multiple-orifice plate

Summary of Contents for DUOJET Series

Page 1: ...KAT B 1912 Edition2 01 18 Operation and Maintenance Instructions VAG DUOJET Automatic Air Valve...

Page 2: ...nstallation note 6 4 4 1 Installation position downstream from pumps 7 4 4 2 Installation in standpipes 7 4 4 3 Discharging splashing or surge water 7 4 5 Assembly instructions and fittings 8 5 Set up...

Page 3: ...ng pressure medium temperature please refer to the product rela ted documentation KAT 1912 A For any alternative operating conditions and applications the manufacturer s written approval must be obtai...

Page 4: ...waste water For information about the corresponding temperature limits please refer to the product related technical documentati on KAT A 1912 In case of alternative operating conditions and applicat...

Page 5: ...e performance data The small venting cross section is for venting small amounts of air during operation under full internal overpressure Picture 6 Air release small cross section Installation should t...

Page 6: ...y 600 mm DN 600 1 2 3 4 1 Venting valve 2 Manually operated air inflow and release flush valve 3 Central stop valve 4 Additional flush and discharge valve 4 2 3 Water flow rate The water flow rate asc...

Page 7: ...ities during the filling process If the VAG DUOJET Automatic Air Valve is installed directly on the standpipe there is a risk of the ball closing prematurely To prevent premature closing we recommend...

Page 8: ...sidue or dirt particles are present in the pipeline they may clog the installation while the pipeline is being purged This may impair the function of the valve or even block it In particular after rep...

Page 9: ...shaft as well as drain Condition of measures for thermal insulation Condition of additional protective measures against infiltration of dirt microbes and rain water in the shaft 6 3 1 Design The desig...

Page 10: ...disassemble and remove foreign matter Internal pressure too low To achieve tightness internal pressure must be at least 3 m water column Replace gasket with a low pressure gasket 0 1 1 bar Deposits f...

Page 11: ...Edition2 01 2018 VAG GmbH Carl Reuther Str 1 68305 Mannheim Germany Tel 49 621 749 0 Fax 49 6 21 749 2153 info vag group com www vag group com...

Reviews: