MECHANICAL INSTALLATION 

机械安装

 

6.4.1  

ViscoSense

®

2 interface box 

传感器界面盒

 

1.  Install the ViscoSense

®

2 interface box in a suitable location, free from excessive vibrations, 

humidity and excessive temperature variations. 

界面盒应安放在适合的地方,避免过渡振动以及

温湿度变化。

 

2.  The maximum distance between sensor and the interface box is determined by the cable length 

from the sensor, being approx. 5 metres. 

传感器与界面盒之间的距离是由传感器电缆长度决定

的,大约

5

米。

 

3.  Allow sufficient space for installation of cables and for servicing. 

留有充分空间以便安装电缆和服

务需要。

 

 

6.4.2  

ViscoSense

®

2 housing 

传感器安放室

 

1.  Remove dust caps from sensor housing and install housing stress-free, with shutoff valves and 

bypass valve in the fuel piping as illustrated in Figure 6. Take care that the flow direction is in 
accordance with the indication on the housing (inlet, outlet and arrow) as illustrated in figure 8. 
Support inlet and outlet piping sufficiently. 

除去防尘盖,根据图

6

所示,安装仓室,止阀及辅助阀

门。按图

8

所示,根据仓室表面指示,注意流动方向

(

入口,出口及箭头

)

,充分固定入出口管路。

 

 

These shutoff valves and bypass valve are not furnished by VAF Instruments. 

这里的止阀及旁通阀非

VAF

提供。

 

2.  Note that the distance between fuel heater and sensor housing inlet should not exceed 4 metres. 

注意:燃油加热器与探头安放仓室入口间的距离不应超过

4

米。

 

3.  To protect the instrument from excessive vibrations, which can cause malfunctioning of the 

instrument, it is recommended to: 

为防止仪器因过渡振动引起的误操作,建议:

 

Install the ViscoSense

®

2

 

as low as possible in the fuel system close to a solid structure or 

beam. 

在燃油系统中尽可能低的安装传感器,并靠近稳固结构或梁。

 

Install suitable pipe clamps at both sides of the ViscoSense

®

2 sensor. 

在传感器两侧安装适当的管夹。

 

4.  Allow at least 50 cm clearance to the sensor housing, to be able to take out the measuring sensor 

for service. 

预留至少

50

公分距离,以便于维修服务时取出探头。

 

 

 

Summary of Contents for VISCOSENSE 2

Page 1: ...structions for installation operation and maintenance 761 VISCOSENSE 2 Viscosity Sensor Interface box Valid for ViscoSense 2 serial number from 87600 87600 Publication nr TIB 761 CN GB 0715 Supersedes...

Page 2: ...s 15 6 4 Mechanical installation 16 6 4 1 ViscoSense 2 interface box 16 6 4 2 ViscoSense 2 housing 16 6 4 3 To assemble ViscoSense 2 sensor 19 6 5 Electrical installation 20 6 6 Connection of sensor t...

Page 3: ...5 Diagnostic information 34 16 CERTIFICATES 36 17 DRAWINGS 37 17 1 ViscoSense 2 sensor and sensor housing 37 17 1 1 ViscoSense 2 sensor housing with sensor installed 37 17 2 ViscoSense 2 interface box...

Page 4: ...afe and correct installation and operation read this manual completely before installing the equipment and starting operations ViscoSense 2 sensor from serial numbers 70000 and interface box from seri...

Page 5: ...ttention to specific types of information A warning to use caution In some instances personal injury or damage to the ViscoSense 2unit or control system may result if these instructions are not follow...

Page 6: ...of this manual no responsibility for errors or omissions is assumed Neither is any liability assumed for damages resulting from the use of the information contained herein Specifications can be change...

Page 7: ...h results in a stable control of the viscosity The ViscoSense 2 sensor is used to measure the actual viscosity of the fuel oil The signal from the sensor is compared to the setpoint of a viscosity con...

Page 8: ...mechanically protected by a stainless steel flowtube with 3 oval slits It is supplied with 5 metres of signal cable for connection to the interface box The ViscoSense 2 Interface box is a wall mount...

Page 9: ...of the pendulum via a feedback circuit In this way the pendulum is kept in vibration at its resonance frequency 3 2 1 4 Measuring the resulting frequency at two specific values of phase difference yie...

Page 10: ...nt PT100 Accuracy Viscosity 2 instantaneous 2 0 5 mPa s Temperature 1 C 1 Measuring range 0 200 C 0 200 Material Sensor Stainless steel 316L Coating Teflon Signal cable length 5 metres integrated with...

Page 11: ...Output Viscosity Active output 4 20 mA current loop 4 20mA Range 0 25 50 mPa s depending on range ViscoSense 2 maximum load 400 Ohm 400 Temperature Active output 4 20 mA current loop 4 20 mA Range 0...

Page 12: ...cess liquids Always use insulated tools when working on electrical installations Ensure that local safety regulations are met when installing and operating the equipment All personnel who operate and...

Page 13: ...amage The ViscoSense 2 sensor has a special Teflon coating on the pendulum Damage of the coating will influence the working of the sensor Special care should be taken not to scratch or damage the Tefl...

Page 14: ...number when contacting the factory or local service representative A ViscoSense 2 unit may be part of a complete VAF viscosity control system For information and instructions covering the other compon...

Page 15: ...f the piping is smaller than the inner diameter of the ViscoSense 2 housing the transitions between the two diameters should be tapered The inner diameter of the ViscoSense housing should not be small...

Page 16: ...o dirt can enter the sensor Insulate the pipes and the sensor housing well to avoid any temperature loss of the fluid When fuel viscosity is 500 mPa s or thicker it is recommended to wrap steam tracin...

Page 17: ...n Figure 6 Take care that the flow direction is in accordance with the indication on the housing inlet outlet and arrow as illustrated in figure 8 Support inlet and outlet piping sufficiently 6 8 Thes...

Page 18: ...ecially movement in the direction of the pendulum movement see drawing angular movement around the sensor axis Therefore there must be two supports to the inlet and outlet perpendicular to the pipe an...

Page 19: ...re 6 Sensor installation diagram 6 The angular position of the supports must always be 90 in relation to the sensor 90 The distance from the flange to the support should be two times the diameter of t...

Page 20: ...handling 4 Install sensor carefully in housing with the closed surface facing the flow illustrated in figure 8 8 Make sure the flow tube closed surface is pointing towards the inlet of the sensor hous...

Page 21: ...TRICAL INSTALLATION Provide correct supply power to the interface box In order to maintain proper EMC protection a shielded cable should be used for 4 20 mA output signals Recommended cable twisted pa...

Page 22: ...nse 2 sensor through gland and connect wires to terminal J6 in accordance with Figure 12 12 J6 3 Feed cable for 4 20 mA viscosity and temperature output signals through the cable glands and connect wi...

Page 23: ...closing the cover again 6 Close the cover of the interface box 6 6 CONNECTION OF SENSOR TO INTERFACE BOX Figure 10 Tighten the cable gland with a spanner 10 Figure 11 Install the numbered wires in th...

Page 24: ...23 Figure 12 External connections at interface box 12...

Page 25: ...booster pump in the fuel system and after approximately 15 minutes close bypass valve L 15 L 6 Switch on power supply to the ViscoSense 2 system Depending upon the viscosity of the liquid it can take...

Page 26: ...A clean operating environment ViscoSense 2 interface box installed in accordance with the installation instructions given Operation of the ViscoSense 2 interface box and related control system in acc...

Page 27: ...ViscoSense 2 sensor assembly 1 8 6 Take out the ViscoSense 2 sensor 7 Do not remove the flow tube do not stick any object in between the flow tube and pendulum 8 Flush the space between the tube and...

Page 28: ...will require that the correct settings for this sensor are made in the interface box To make the correct settings a spare sensor is supplied together with a dongle which can be connected into the int...

Page 29: ...r use The dongle is meant to be used for 1 sensor only and can be disposed according to local rules The dongle contains electronic components and a small battery 10 TAKE OUT OF SERVICE Disconnect the...

Page 30: ...e should carefully be placed in between the flow tube and the pendulum The sensor must be wrapped in protection material preferably where it was shipped in to protect it from damage Both the sensor an...

Page 31: ...nt has the following possible environmentally unfriendly components in minor quantities Sensor Teflon coating on the sensor head Sensor cable Electrical cable with Teflon coating Interface box Electro...

Page 32: ...diagnostic led Viscosity output is lower than expected Actual viscosity is lower than expected E g bunker calculator only gives approx value Dilution with MDO Temperature is higher than expected None...

Page 33: ...gher than the max range Heat up the fluid Actual viscosity is higher than expected E g bunker calculator only gives approx value None ViscoSense 2 interface box is malfunctioning Check diagnostic led...

Page 34: ...shooting Ti too high Ti Decrease Ti Ti High initial overshoot followed by fading oscillation Ti too low Ti Increase Ti Ti 15 4 HOW TO TAKE A HFO SAMPLE FOR ANALYSIS The HFO sample must always be taken...

Page 35: ...wer on Changing U send_setpoint Initializing hardware measuring at 45 degrees left 3 dB point 45 3 dB VCO frequency measurement while phase is 45 degrees 45 measuring at 45 degrees left 3 dB point 45...

Page 36: ...mperature output mA Recovery action attempt Fault description 0 0 Delay retry 15 V power failure Supply drops below 13 V 15 13 0 Actual Delay retry Pendulum not oscillating 4 Actual Delay retry Oscill...

Page 37: ...36 16 CERTIFICATES Certificates are delivered separately...

Page 38: ...37 17 DRAWINGS 17 1 VISCOSENSE 2 SENSOR AND SENSOR HOUSING 17 1 1 ViscoSense 2 sensor housing with sensor installed Figure 18 Dimensions of ViscoSense 2 sensor All dimensions in millimetres 18...

Page 39: ...38 Figure 19 Dimensions of ViscoSense 2 sensor All dimensions in millimetres 19...

Page 40: ...39 Figure 20 Dimensions of ViscoSense 2 sensor All dimensions in millimetres 20...

Page 41: ...40 Figure 21 Dimensions of ViscoSense 2 sensor All dimensions in millimetres 21...

Page 42: ...41 17 2 VISCOSENSE 2 INTERFACE BOX 17 2 1 ViscoSense 2 interface box Figure 22 Dimensions of ViscoSense 2 interface box All dimensions in millimetres 22...

Page 43: ...Memory EPROM Erasable Programmable Read Only Memory Hz Hertz Frequency IEC International Electrotechnical Commission IOM Installation Operation and Maintenance JIS Japanese Industrial Standard Kg Kil...

Page 44: ...43 19 PARTS LISTS Spare parts 0279 0096PH consisting of 0279 0096 ViscoSense 2 sensor 0279 0102 dongle 0279 0096PH 0279 0096 0279 0102 19 1 VISCOSENSE 2 SENSOR...

Page 45: ...1 0279 0096 ViscoSense 2 sensor ass y incl items 2 3 and 4 2 3 4 2 1 0630 3022 O ring viton O ID 25 12 x 1 78 mm 3 2 1731 0404 Hex socket set screw M4 x 4 mm DIN 916 AISI 316 4 1 0442 0326 Flow tube...

Page 46: ...ent this remaining at the discretion of the contractor Subarticle 3A shall equally apply if repair or replacement takes place at the site where the product has been assembled installed All costs accru...

Page 47: ...to any guarantee regardless of how it is referred to If without previous written approval from the contractor the principal commences disassembly repair or other work on the product or allows it to be...

Page 48: ...ocity Fuel velocity depends on the capacity of the circulation booster pump and the inner diameter of the pipe that is used A larger inner diameter will give a slower fuel velocity The recommended fue...

Page 49: ...f hot 130 C with colder 80 C fuel to a fuel with a single temperature 130 C 80 C Compensation of pressure pulses Prevention of a thermal shock of the engine when changing over from HFO to MDO Remarks...

Page 50: ...electric There must be two heaters placed parallel in the system Only one heater should be switched on The other one should be clean and on standby Booster pump There should be two booster pumps One a...

Page 51: ...Dordrecht The Netherlands P O Box 40 3300 AA Dordrecht The Netherlands T 31 0 78 618 3100 F 31 0 78 617 7068 sales vaf nl www vaf nl Specifications subject to change without notice Agents and distrib...

Reviews: