Automatic reset
P11.1
AUTOMATIC
RESET
0: Disabled
1: Enabled
The automatic reset function deletes fault state when the fault cause has been eliminated and
the wait time P11.2 has elapsed. Parameter P11.4 determines the maximum number of auto-
matic resets that can be effected during the trial time set by parameter P11.3. The time count
starts from the first automatic reset. If the number of faults detected during the trial time ex-
ceeds the values of trials, the fault status becomes permanent and a reset command is need-
ed.
P11.2 W
AIT
TIME
Time after which the converter attempts to restart the motor automatically after the fault has
been eliminated.
P11.3 T
RIAL
TIME
Total time for reset attempts.
P11.4 N
UMBER
OF
TRIALS
Trials attempted during time P11.3.
P11.5 R
ESTART
FUNCTION
Start function after an automatic fault reset.
0: Start with ramp
1: Flying start
2: As defined in P2.3