Parameter description
vacon • 46
Service support: find your nearest Vacon service center at www.vacon.com
3
3.7
Mechanical brake
P7.1
B
RAKE
OPEN
FREQUENCY
P7.2
B
RAKE
OPEN
CURRENT
Thresholds that must be reached for external brake open at start.
If P7.1 > 0Hz, frequency reference is internally limited to P7.1 + 0.1 Hz until the brake is re-
leased.
Fault 56 Brake Time Out is triggered if the thresholds in P7.1 and P7.2 are not reached within
3s from Start command.
P7.3
B
RAKE
CLOSE
FREQUENCY
The brake is closed when the start command is low and output frequency is below this thresh-
old. Possible delay in P7.4.
P7.4
B
RAKE
CLOSE
DELAY
Respected in any stop condition (quick, fault, no enable), apart direct control from ASi input,
when the signal goes low.