vacon • 57
Parameter description
3
P10.15
R
ESPONSE
TO
S
AFE
T
ORQUE
O
FF
0: No action
1: Warning
2: Fault, not stored in history
3: Fault, stored in history
Safe Torque Off disabled.
P10.16
I
NPUT
PHASE
FAULT
0: No action
1: Warning
2: Fault
Input phase missing.
P10.17
I
NPUT
PHASE
FAULT
RIPPLE
LIMIT
Sensitivity for input phases check
0: internal value (default)
1-75: sensitivity from maximum(1) to minimum (75)
P10.18
M
OTOR
TEMPERATURE
INITIALIZATION
Setting of estimated motor temperature at power on
0: initialized at minimum value
1: initialized at constant value from P10.19
2: initialized at last previous value, with P10.19 used as factor
P10.19
M
OTOR
TEMPERATURE
INITIAL
VALUE
If P10.18= 1, motor temperature is initialized with this value.
If P10.18= 2, motor temperature is initialized with last previous value, multiplied by this value
as % factor.