25.6 - TABLE OF PROGRAMMING PARAMETERS
PARAMETER
VALUE
SUBMENU DESCRIPTION
DEFAULT
CHAPTER
MEMO
MODE
Working mode
STAN
21
STAN
Standard
PRES
Dead man
S.PRE
Mixed
OROL
Timer
T.AP
0.0”-5.0’
Opening time
15”
T.CH
0.0”-5.0’
Closing time
16”
P.APP
0-100%
Partial opening
50%
17
T.PRE
0.5”-10.0”
Pre-blinking time before opening
1.0”
13
NO
Function disabled
T.PCH
0.5”-10.0”
Pre-blinking time before closing
NO
13
NO
Pre-flashing during closing equal to
T.PRE
T.AR
0.1”-2.0”
Backlash time
NO
23.2
NO
Function disabled
R.INV
0.1”-2.0”
Delay at inversion
0.5”
9.1
NO
Function disabled
FRE.A
Brake during opening phase
SI
9.1
SI
Function enabled
NO
Function disabled
FRE.C
Brake during closing phase
SI
9.1
SI
Function enabled
NO
Function disabled
SEN.A
0.0A-9.9A
Amperometric sensor level during opening
0.0A
12.1
SEN.C
0.0A-9.9A
Amperometric sensor level during closing
0.0A
12.1
ST.AP
Start during the opening phase
PAUS
19
PAUS
The door stops and pauses
CHIU
The door immediately starts closing
NO
The door continues to open (the command is
ignored)
ST.CH
Start during the closing phase
STOP
19
STOP
The door stops and the cycle is considered as
complete
APRE
The door re-opens
ST.PA
Start during pause
CHIU
19
CHIU
The door starts closing
NO
This command is ignored
PAUS
The pause time is reset