ENGLISH
- 41 -
20 - REMOTE CONTROL MODE
The HEAVY2 unit is fitted for the connection of an MR series
receiver. The receiver has 4 channels, which can be associated
with the buttons on the remote control and can have the
following functions:
• Channels 1 and 2 trigger the opening cycle according to the
setting of the parameter
RX
:
START
: channel 1 is equivalent to START command and
channel 2 to PARTIAL START command
APCH
: channel 1 is equivalent to the command OPEN and
channel 2 to the command CLOSE
• Channel 3 is equivalent to the STOP command
• Channel 4 operates according to the setting of the
parameter
AUX
:
MON
: monostable. The contact of an option relay (REL1-2-3)
set as courtesy light is kept closed as long as the channel is
active.
BIST
: bistable. The contact of an option relay (REL1-2-3)
set as courtesy light is switched every time the channel is
activated.
TIM
: timer. The contact of an option relay (REL1-2-3) set as
courtesy light is kept closed for the time set. If the channel is
again activated, the time count is reset.
TOUT
: time out. The contact of an option relay (REL1-2-3)
set as courtesy light is kept closed for the set time.
If the channel is again activated, the relay contact is opened.
PRES
: force dead man mode. At each activation of the
channel the unit switches between the operating mode
set and the dead man mode.
21 - OPERATING MODES
The operating mode of controls depends on the settings of the
parameter MODE.
•
Pulse mode
(
MODE
=
STAN
)
A command opens the door.
The manoeuvre ends when the limit switch is activated,
when another command is received or when a safety device
is activated. When the automatic closing is enabled the door
closes after the pause time set (parameter
CH.AU
)
•
Clock mode
(
MODE
=
CLOCK
)
This function allows to delay the opening of the door through
an external clock.
The operation is identical to the mode
STAN
, but the pause
time count is suspended until the contact of the device
connected to an input configured as
STRT
,
ST.PE
or
APRE
is closed.
To use this feature, you must enable the automatic closing
(parameter
CH.AU
)
•
Dead man mode
(
MODE
=
PRES
)
The command must be kept active for the entire duration of
the movement of the door; when the command is
suspended the door stops immediately. In this mode, the
START command launches alternately the opening and
closing.
•
Mixed mode
(
MODE
=
S.PRE
)
The opening movements are controlled by pulses and the
closing ones in dead man mode.
A door that moves in dead man mode stops if a safety device
is activated; it is not possible to reverse the movement of the
door as during normal operation.