VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 45 of 63
Multiple PEFS Cylinder Installations
Pressure Low switch
For multiple LOP cylinder installations, which have a common LOP actuation system, a single
cylinder low pressure switch may be fitted either to:
•
one of the cylinder valves’ low pressure switch ports
•
at any suitable point in the LOP actuation system
For multiple ROP cylinder installations, a cylinder low pressure
MUST
be fitted to each cylinder
valve.
Discharge Pressure Switch
For multiple LOP and ROP cylinder installations a discharge pressure switch
MUST
be fitted to each
cylinder valve to allow redundancy in shutdown should a valve fail to operate correctly.
The activation of a discharge pressure switch (opening of circuit) will initiate the Discharged LED on
the MKII display and also the Alarm LED. The Alarm sequence is linked to Engine shutdown.
This pressure switch arrangement allows the equipment to shutdown if a pneumatic or manual
actuation device is operated.
Connecting PEFS pressure switches to the control module
Figure 62 - PEFS pressure switch wiring