VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 43 of 63
Step 3.
Refit brass cover and tighten the gland until cable is sealed.
Step 4.
Use jiffy splice or Deutsch cable connectors to connect the LHD
cable to field wiring back to the VS-MKII control module.
Deutsch connectors should always be used where a break
away connection is required. Connector pin size - 0.5 to 1.0 mm
Remember: Always check crimp integrity by giving a slight tug
on each wire.
Table 26 - Installing LHD cable
Note: If electrical detection is not being used the circuit needs to be switched off using Channel b.
.
Connecting LHD cable to the control module
Figure 59 - Detection circuit 1 wiring