VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 39 of 63
Step 3.
Remove safety pin and loosen lock nut.
Rotate switch assembly so that the circuit card is accessible.
Remove resistor (R1) on each unit before the last.
The last unit’s resistor remains to act as the EOL.
Step 4.
Twist the two white wires together and the two red wires together
from each cable.
This is what will set the parallel circuit up to read the EOL.
Step 5.
Connect the wires to the terminal block.
A slight tug on the cable will confirm that the wires are securely
clamped.
Tighten the grommets and replace the cover
Table 24 - Installing multiple electrical actuators
Note: If an electrical actuator is not being used the circuit will need to be switched off using Channel A
.