VS-MKII Control System
Chubb Fire & Security Pty Ltd
Technical Manual
Page 31 of 63
Installing the MKII Module
Mount the MKII control module at a suitable location in the equipment away from the fire hazard area. For
wiring purposes the preferred location is within the equipments cabin.
•
The module can be secured on any surface of
the equipment using the four mounting holes
and the bolts supplied.
•
When installing the module the recommended
orientation is for the connectors to be facing
down.
•
The module will not charge the back up battery
pack when the ambient temperature inside
exceeds 40
o
C. Therefore it should not be
positioned in direct sunlight or in contact with
surfaces that are likely to exceed this
temperature on a regular basis.
•
To minimize the effects of electromagnetic
emissions from high energy sources, the VS-
MKII control system input cables should NOT be
run parallel or in close proximity to any cables or
equipment that may produce high RF (radio
frequency) energy, e.g. cabling for RF
transceiver antennas, inverters, motors etc.
Figure 38 - Module dimensions
VS-MKII Display Panel & Audible Alarm
Display settings
The MKII display panel has a series of dip switches located on the PCB (Fig. 41). To access the PCB,
remove the four screw covers (Fig. 39), screws, rear and frame covers (Fig. 40).
Figure 39 - Screw covers & screws Figure 40 - Display cover
Screw cover
Screw