Impossible to arm the machine
BLUE LED doesn’t switch on
Wiring error
Overtemperature of the PCB
Error in the thermal loop
Verify that the alarm, once activated, has tension on
connectors of at least 12 V between GND(5) + SHOOTS(4)
Try to reset. See paragraph 16
In case of unsuccessful restore the PCB can be damaged,
contact the assistance service.
Check there is a sufficient ventilation around the machine.
Warning: in this case shooting time is reset to zero
Reset bombole (Paragrafo 14)
Impostazione tempo di sparo (Paragrafo 12)
Possible fault of: thermocouple, resistance or fuse
cable. Don’t try to repair
Contact the assistance service center.
In large size plants or with more than on fogging system
connected with the same central, in rare situations, it may
occur that there are potential differences between the
equipments and it could be necessary to uncouple.
Press down and then pull
Wiring error
The cylinder does not enter
When you press the reset
button you don’t hear
the sound of the buzzer, the
frontal LEDS are flashing but
the RED LEDS does not reset
Disturbance/ interference
or potential differences
between devices
In the case of strong interference (lightning) can occur a
thermocouple reading error, make a reset.
See paragraph 16.
In case of unsuccessful restore can be occurred a
potential difference or a fault.
Check on the terminal with a tester that when the alarm
system is turned on there is a minimum voltage of 11 V
between - GND (5) + ARM (3).
The plate is raised
Press down and then pull
The Jumper P3 is in the
“SET” position
The cylinder is stuck
in the valve
The cylinder doesn’t go out
See shooting time setting at paragraph 12
The jumper P3 stands in
the “RESET” position
Setting the shooting time, the
buzzer does not sound and
the LEDs do not flash
BLUE LED is flashing
The buzzer emits a continuous
sound
BLUE and RED LEDS
are flashing alternately
Overvoltage power line
(120/230 V)
Cannot arm,
BLUE LED doesn’t
switch on
Wiring error
Test the terminal that there is a minimum voltage
between 11V - GND (5) + ARM (3),
when the anti-theft system is activated
21