www.uponor-usa.com • www.uponor.ca

18

Uponor Climate Co˘ntrol™ - Multifunction Installation Guide

19

The Pump Relay Box 
comes with a ¾-inch 
thread for mounting to 
circulators. Some 
manufacturers produce 
pumps that allow for 
two electrical 
connections on the 
motor housing. (See 

Figure 4-13

.) When 

this option is available, 
the Pump Relay Box 
will thread directly into 
this tapping for easy 
mounting. When this 
option is not available, 
use standard electrical 
boxes with pump relays.

 

 
 

Figure 4-13. Single- and double-gang electrical box with switch

Off

Call

On

Au

to

Line Voltage In

( 115v )

L

N

Black

Red

White

or Circulator

Wire to Pump 

( 2 amps Max )

On

( 2 amps Max )

or Circulator

Wire to Pump 

L

N

Black

Call

Au

to

Line Voltage In

( 115v )

Black

Red

White

White

Red

Wire to Pump 

or Circulator

( 2 amps Max )

On

Au

to

Call

Pump 

Re

la

y (A9013030)

Pump 

Re

la

y (A9013030)

Pump 

Re

la

y (A9013030)

Off

Call

On

Au

to

Line Voltage In

( 115v )

L

N

Black

Red

White

or Circulator

Wire to Pump 

( 2 amps Max )

On

( 2 amps Max )

or Circulator

Wire to Pump 

L

N

Black

Call

Au

to

Line Voltage In

( 115v )

Black

Red

White

White

Red

Wire to Pump 

or Circulator

( 2 amps Max )

On

Au

to

Call

Pump 

Re

la

y (A9013030)

Pump 

Re

la

y (A9013030)

Pump 

Re

la

y (A9013030)

The Climate Co˘ntrol - Multifunction system offers additional flexibility and 
can be daisy-chained — where two pumps turn on simultaneously (e.g., in a 
heat exchanger application when the primary pump needs to turn on at the 
same time as the secondary pump). The two connectors that come with each 
Pump Relay Box are universal (i.e., the ports are not dedicated).  
(See 

Figure 4-12

.)  

Figure 4-12. Typical connection of multiple pumps using one control signal

Auto

Manual

Top View

On

Tx

Run

Rx

Port 1

Input 1

Operate

MMI

Port 8

Input 8

Port 3

Port 2

Port 4

Port 5

Input 2

Input 3

Input 4

Input 5

Port 6

Input 6

Port 7

Input 7

Rx

Tx

Intercon

Return Sensor

Supply Sensor

Top View

Manual

Auto

Supply-and-return 

Dual Sensors (A9013001)

To Climate Co˘ntrol 

Main Panel

Pump Relay Box (A9013030)

Pump Relay Box (A9013030)

Summary of Contents for Climate Control-Multifunction

Page 1: ...Uponor Climate Co ntrolTM Multifunction Installation Guide RA DIAN T HEATING SYST EMS CLIMATE CO NTROL MULTIFUNCTION INSTALLATION GUIDE...

Page 2: ...stic Hot Water DHW 3 Zone Pump Control 3 Mixing 3 Snow Melting 3 Semi automatic Control 4 Fully Automatic Control 4 Slab Idle 4 High Temperature 4 Pump Exercising 4 Section 3 Safety Measures 5 Section...

Page 3: ...tion s architecture supports up to eight outputs e g pumps modulating valves boilers The unused ports can support additional zone pumps within the system rather than adding other control elements View...

Page 4: ...ol Multifunction unit monitors the return boiler temperature If the temperature drops too low the system will begin to close the three way valves If this option doesn t work the high temperature pumps...

Page 5: ...set temperature High Temperature If the control supports high temperature control the system will turn on the high temperature pump until the demand call ends However if the minimum boiler return temp...

Page 6: ...following list Installation guide Main control panel Outdoor sensor Supply and return sensor or dual sensor Data key mounted inside display enclosure Important Read the following installation instruc...

Page 7: ...nstalling any additional screws Mark the location with a pencil or pen if anchors are being used See Figure 4 2 6 Install the remaining screws to finish mounting the control Optional Control Panel Mou...

Page 8: ...en active LEDs for the inputs and outputs will turn green On Tx Run Rx Port 1 Input 1 Operate MMI Port 8 Input 8 Port 3 Port 2 Port 4 Port 5 Input 2 Input 3 Input 4 Input 5 Port 6 Input 6 Port 7 Input...

Page 9: ...Control A9012010 for space heating Auto Man A Terminal B Terminal A B Power Space Heating High Temp DHW Typical heating device e g boiler Top View Side View Port 1 Port 8 Port 3 Port 2 Port 4 Port 5 P...

Page 10: ...d snow melting The Climate Co ntrol hydronic controller can connect to any 0 10VAC motor and valve using the Uponor Modulating Valve Control A9063020 Note The motor must be 75 milliamps or less from a...

Page 11: ...maximum of three amps in a variety of applications Common types of uses include primary secondary and domestic hot water DHW pumps As an added feature the Climate Co ntrol Multifunction hydronic contr...

Page 12: ...ite White Red Wire to Pump or Circulator 2 amps Max On Auto Call Pump Relay A9013030 Pump Relay A9013030 Pump Relay A9013030 Off Call On Auto Line Voltage In 115v L N Black Red White or Circulator Wir...

Page 13: ...elt connection with slab sensing Auto Active Remote Push Button optional Top View Side View Port 1 Port 8 Port 3 Port 2 Port 4 Port 5 Port 6 Port 7 Uponor Snow Melt Control A9013051 10K Slab Sensor To...

Page 14: ...d properly on the sheet provided The wiring compartments are enclosed The display is lit and showing the Uponor logo default date and time and outdoor temperature Initial Setup The Display Unit The di...

Page 15: ...path Uponor Screen Settings System Settings Backlight The use of the symbol indicates pressing the OK button The following settings are available Backlighting On Display remains at 100 intensity at al...

Page 16: ...hannel is active If not active 0 0 F displays Supply and Return Temp Display current temperature for the supply and return sensors if the sensors are connected If not connected 0 0 F displays Press or...

Page 17: ...limate Co ntrol Multifunction the most versatile control in mechanical room functionality allows the installer to tell the control which devices are connected and which functions to use If a port has...

Page 18: ...K button The following selections are available DHW Setting Set the requirement for the tank temperature through the tank sensor Demand Input Set the input number for a connection that will start the...

Page 19: ...nformation correctly to match the system then press OK to accept the information SM Snow melt Function The following selections are available SM Channel This sets a reference number This does not corr...

Page 20: ...or ice Outdoor Hi Low Temp This setting indicates the outdoor temperatures all snow melt functions will no longer run SM Delta T This setting indicates the target differential temperature between the...

Page 21: ...Solutions Notes Nothing showing on the display Display appears dark blank No power to control unit Connection issue between control and display Check 24VAC power supply and connection Check cable for...

Page 22: ...55124 USA Tel 800 321 4739 Fax 952 891 1409 Web www uponor usa com Uponor Ltd 655 Park Street Regina SK S4N 5N1 CANADA Tel 888 994 7726 Fax 800 638 9517 Web www uponor ca ClimateCtrl_InsG_1 08 Copyri...

Reviews: