background image

www.uponor-usa.com • www.uponor.ca

16

Uponor Climate Co˘ntrol™ - Multifunction Installation Guide

17

The valve relay comes with a set of LEDs to show the relay's status.  
Terminal strips for wiring connections to the valve motor and a manual 
switch are contained inside the cover. The manual switch, when set to the 
Man position, overrides any control signal coming from the Climate Co˘ntrol - 
Multifunction controller and allows the installer to set the valve position. 

 

 

Caution:

 Failure to return the manual switch to the auto position 

will affect the correct regulation of secondary water temperatures. 
When the valve box is connected properly to the control, the 
power light turns green. The active light turns red whenever the 
control is changing the position of the valve for mixing.

The Climate Co˘ntrol - Multifunction unit supports variable speed injection 
mixing, which requires an Uponor Pump Relay Box (A9013030). (See

 Pump 

Connections

 below for additional information on wiring.) Uponor promotes 

the use of modulating valves rather than injection pump valves due to lower 
power consumption and staying in line with the industry as it moves toward 
modulating and condensing boilers. 

Pump Connections 

Climate Co˘ntrol - Multifunction unit supports on/off operation of pumps

 

(maximum of three amps) in a variety of applications. Common types of uses 
include primary, secondary and domestic hot water (DHW) pumps. As an 
added feature, the Climate Co˘ntrol - Multifunction hydronic controller can 
be configured to run zone pumps on open or spare ports. 

All pumps are quickly and easily connected using Cat5 cables. The Pump 
Relay Box comes with LEDs to show the status of the relay. When the relay 
and the pump are wired correctly, the auto light will turn green when power 
is applied to the circuit. When the system turns on the pump, the Call and 
On lights will turn green. A manual switch is included under the top cover 
of the relay. When this switch is set to the manual position, the On light will 
turn green, provided the auto light is on. When set to the manual position, 
the manual switch overrides any control signal coming from the Climate 
Co˘ntrol - Multifunction controller and allows the pump to run continuously.  
(See 

Figure 4-11

.)

 

 

Caution:

 Failure to return the manual switch to the auto position 

can lead to overheating.

Supply-and-return 

Dual Sensors (A9013001)

Pump Relay Box (A9013030)

Supply Sensor

Return Sensor

Top View

Auto

Manual

White

Red

Black

Auto

On

Call

Side View

To Climate Co˘ntrol 

Main Panel

On

Tx

Run

Rx

Port 1

Input 1

Operate

MMI

Port 8

Input 8

Port 3

Port 2

Port 4

Port 5

Input 2

Input 3

Input 4

Input 5

Port 6

Input 6

Port 7

Input 7

Rx

Tx

Intercon

Figure 4-11:

 Typical wiring of a pump or circulator using Pump Relay Box (A9013030)

 

Summary of Contents for Climate Control-Multifunction

Page 1: ...Uponor Climate Co ntrolTM Multifunction Installation Guide RA DIAN T HEATING SYST EMS CLIMATE CO NTROL MULTIFUNCTION INSTALLATION GUIDE...

Page 2: ...stic Hot Water DHW 3 Zone Pump Control 3 Mixing 3 Snow Melting 3 Semi automatic Control 4 Fully Automatic Control 4 Slab Idle 4 High Temperature 4 Pump Exercising 4 Section 3 Safety Measures 5 Section...

Page 3: ...tion s architecture supports up to eight outputs e g pumps modulating valves boilers The unused ports can support additional zone pumps within the system rather than adding other control elements View...

Page 4: ...ol Multifunction unit monitors the return boiler temperature If the temperature drops too low the system will begin to close the three way valves If this option doesn t work the high temperature pumps...

Page 5: ...set temperature High Temperature If the control supports high temperature control the system will turn on the high temperature pump until the demand call ends However if the minimum boiler return temp...

Page 6: ...following list Installation guide Main control panel Outdoor sensor Supply and return sensor or dual sensor Data key mounted inside display enclosure Important Read the following installation instruc...

Page 7: ...nstalling any additional screws Mark the location with a pencil or pen if anchors are being used See Figure 4 2 6 Install the remaining screws to finish mounting the control Optional Control Panel Mou...

Page 8: ...en active LEDs for the inputs and outputs will turn green On Tx Run Rx Port 1 Input 1 Operate MMI Port 8 Input 8 Port 3 Port 2 Port 4 Port 5 Input 2 Input 3 Input 4 Input 5 Port 6 Input 6 Port 7 Input...

Page 9: ...Control A9012010 for space heating Auto Man A Terminal B Terminal A B Power Space Heating High Temp DHW Typical heating device e g boiler Top View Side View Port 1 Port 8 Port 3 Port 2 Port 4 Port 5 P...

Page 10: ...d snow melting The Climate Co ntrol hydronic controller can connect to any 0 10VAC motor and valve using the Uponor Modulating Valve Control A9063020 Note The motor must be 75 milliamps or less from a...

Page 11: ...maximum of three amps in a variety of applications Common types of uses include primary secondary and domestic hot water DHW pumps As an added feature the Climate Co ntrol Multifunction hydronic contr...

Page 12: ...ite White Red Wire to Pump or Circulator 2 amps Max On Auto Call Pump Relay A9013030 Pump Relay A9013030 Pump Relay A9013030 Off Call On Auto Line Voltage In 115v L N Black Red White or Circulator Wir...

Page 13: ...elt connection with slab sensing Auto Active Remote Push Button optional Top View Side View Port 1 Port 8 Port 3 Port 2 Port 4 Port 5 Port 6 Port 7 Uponor Snow Melt Control A9013051 10K Slab Sensor To...

Page 14: ...d properly on the sheet provided The wiring compartments are enclosed The display is lit and showing the Uponor logo default date and time and outdoor temperature Initial Setup The Display Unit The di...

Page 15: ...path Uponor Screen Settings System Settings Backlight The use of the symbol indicates pressing the OK button The following settings are available Backlighting On Display remains at 100 intensity at al...

Page 16: ...hannel is active If not active 0 0 F displays Supply and Return Temp Display current temperature for the supply and return sensors if the sensors are connected If not connected 0 0 F displays Press or...

Page 17: ...limate Co ntrol Multifunction the most versatile control in mechanical room functionality allows the installer to tell the control which devices are connected and which functions to use If a port has...

Page 18: ...K button The following selections are available DHW Setting Set the requirement for the tank temperature through the tank sensor Demand Input Set the input number for a connection that will start the...

Page 19: ...nformation correctly to match the system then press OK to accept the information SM Snow melt Function The following selections are available SM Channel This sets a reference number This does not corr...

Page 20: ...or ice Outdoor Hi Low Temp This setting indicates the outdoor temperatures all snow melt functions will no longer run SM Delta T This setting indicates the target differential temperature between the...

Page 21: ...Solutions Notes Nothing showing on the display Display appears dark blank No power to control unit Connection issue between control and display Check 24VAC power supply and connection Check cable for...

Page 22: ...55124 USA Tel 800 321 4739 Fax 952 891 1409 Web www uponor usa com Uponor Ltd 655 Park Street Regina SK S4N 5N1 CANADA Tel 888 994 7726 Fax 800 638 9517 Web www uponor ca ClimateCtrl_InsG_1 08 Copyri...

Reviews: