Uplift Desk Power & Data Rail Installation Instructions Manual Download Page 16

© UPLIFT Desk

 • 800-349-3839 • 512-614-3152 • [email protected] • upliftdesk.com

16

Power infeeds

The recommended electrical system for the UPLIFT 
Power and Data Rail is the Byrne 8-Trac System. How-
ever, we have also designed the Power and Data Rail 
to accept the Dekko 8-Wire System. This can help 

prevent any delays if one of those two suppliers is ex

-

periencing long lead times. 

The first type of power infeeds for the UPLIFT Pow

-

er and Data Rail is the Plug-in infeed (see fig.1) which 
plugs into either a wall outlet or a floor outlet and can 

be installed by anyone. Plug-in feeds are supplied by 
a single 20 amp circuit that typically supplies your of-

fice wall outlets.  

The second type of power infeed is the Hardwire in-

feed (see fig.2). The hardwire infeed connections must 

be made by a licensed electrician. 

The Power infeed accommodates up to four 20 amp circuits and consists of four line conductors, 

two neutrals, and two grounds. Per National Electrical Code (NEC) requirements, up to 13 duplex 

receptacles may be used per circuit, with a total of 52 available receptacles if all four circuits are 
used. The line conductors are 12 AWG, and share a 12 AWG ground and a 10 AWG neutral conduc-
tor. The fourth circuit is isolated and dedicated and is serviced by its own line, neutral, and isolated 

ground conductors. The Byrne 8-Trac System can be wired in both single and three-phase config

-

urations, 240/120V, 208/120V respectively (see Byrne 8-Trac wiring diagram below). 
This power rail system utilizes (4) circuits; (3) for general purpose that share a common neutral and 
ground, and (1) circuit that has a dedicated neutral and ground. This dedicated circuit is sometimes 
used as the “computer” circuit since it does not share a neutral conductor, thereby reducing the 
chance for electrical noise originating from other loads that may be plugged in. But many users plug 

their computers into any of the 4 circuits without issues. Byrne duplex receptacles are marked as 1, 2, 

3, and 4. Receptacles marked 1, 2, and 3 connect to the three general purpose circuits and the recep-
tacle marked 4 connects to the dedicated circuit. IF you optionally choose to only plug computers 
into the dedicated circuit you may need to use additional power infeeds and an electrical designer 
can help with this - as a general rule, you can assume 250W (2.08A) for each computer receptacle 
and 180W (1.5A) for each general purpose receptacle when calculating for each 20A circuit.

Electrical Wiring

Fig. 1 - Plug-in power infeeds

Fig. 2 - Hardwire power infeeds

24’’

24’’

Hardwire power infeed wiring diagram

Circuit 1

Circuit 2

Circuit 3

Circuit 4

Gray

White

Green/Yellow

Green

Pink

Blue

Red

Black

Neutral 2

Neutral 1

Iso Ground

Ground

Hot 4

Hot 3

Hot 2

Hot 1

IMPORTANT:

 

All hard wired electrical connections must be made by a licensed electrician. 

Refer to all warnings at the beginning of this manual.

Summary of Contents for Power & Data Rail

Page 1: ...assistance visit upliftdesk com call 800 349 3839 or email support upliftdesk com Patent Pending 2020 UPLIFT Desk All Rights Reserved 355lb two person assembly Power Data Rail Modular system for power...

Page 2: ...ckets PDC005 PRV Privacy Panels shipped separately Short wire trays PDC005 TRAY SHT Long wire trays PDC005 TRAY LNG Long rail assembly PDC005 RAIL LNG Short rail assembly PDC005 RAIL SHT Square post P...

Page 3: ...r access to power outlets is limited and eliminate cable clutter and the need for extension cords The Power and Data Rail was designed to position UPLIFT V2 and V2 Commercial desks with con sistent al...

Page 4: ...two M6x6 Set screws so the Upper post can slide If you are using the Power and Data Rail with UPLIFT V2 Commercial desks slide the Upper post until the bottom edge is aligned with the first indicator...

Page 5: ...t were included with each post to attach the feet as shown to the bot tom of each post assembly The oval power infeed hole should be facing to the left or right of the foot This way the holes will be...

Page 6: ...tep 2 Turn each Rail assembly over and loosen the two screws in each of the Rail extension washers using the 3mm Allen wrench Do not remove the screws com pletely This will allow the Rail extensions t...

Page 7: ...ng Posts and Rail assemblies down the row following Steps 3 and 4 above until all of the Rail assemblies are attached to the posts Then continue to move your UPLIFT V2 desks into place locating the de...

Page 8: ...be connecting Rail assemblies to other sides of the Square posts Follow the same Rail extension attachment process as shown in the section Assembly Linear Configurations Step 3 page 6 The type of pos...

Page 9: ...e Upper post until the bottom edge is aligned with the first indicator line For UPLIFT V2 frames slide the Upper post to the second indicator line Once in place tighten the Set screws again and con ti...

Page 10: ...ction box for hardwire pow er infeeds with the Power infeed hole facing the pow er source If you are assembling a Dog Bone Shape configura tion you will need two sets of 120 Degree and Square posts No...

Page 11: ...desks to create consistent spacing between the desks Dog Bone The Dog Bone configuration includes two 3 Pack con figurations bridged by pairs of 24 deep rectangular desks in between This example illu...

Page 12: ...ding a row of 42 desks but only 21 5 for a row of 72 desks Run your Power infeed in the orientation shown from the middle of the Rail through the Rail extension and down the Post that is nearest to th...

Page 13: ...re posts and will require two Jumpers to connect all three Rails Follow the Power infeed and Jumper installation pro cedures described in Steps 1 and 2 of this section You may find it helpful to tempo...

Page 14: ...ble after connection to Power block to ensure they are completely locked in place There are two Jumper connection points on each end of the Power block You can use either one or both as needed per you...

Page 15: ...es to ensure they are locked in Snap a Faceplate into the opening and around the Receptacles and repeat these steps for the remaining Power blocks If one side of the Rail is not receiving Receptacles...

Page 16: ...ac System can be wired in both single and three phase config urations 240 120V 208 120V respectively see Byrne 8 Trac wiring diagram below This power rail system utilizes 4 circuits 3 for general purp...

Page 17: ...B 15 panel mount solder style www Byrne com Step 1 If you are running data cables UL Listed DUXR or Recognized DUXR2 jacks are required Jacks and cables are not included PicktheDataplateadapterwhichwi...

Page 18: ...ng the in structions provided with the jack Step 4 Pullthefinishedcable jackthroughoneofthesquare holes in the Data plate from the back side Snap the jack into the one of the Data plate adapters you s...

Page 19: ...e M5x6 screws in the center of the Rail Cover and refer to the instructions that came with the Privacy panel brackets Step 2 If you re installing Wire trays refer to the instructions that come with th...

Page 20: ...the UPLIFT Desk website upliftdesk com Excerpts or copies may not be forwarded to third parties or used in any other published form without the prior written consent of UPLIFT Desk These instructions...

Reviews: