81
6
Useful Functions
81
U
se
fu
l F
un
ct
io
ns
Chapter
6
06 (0x06) Write Single Register
The values of slave holding registers are changed (rewritten).
When broadcast (0) is specified, holding registers of all slave devices with the same address will be
rewritten.
The holding register address and data to be changed are specified in the request.
* Be sure to specify the setting code prior to writing setting values for each item.
Example) Changing the value of compensation (address 40059) to 20 (0x0014).
Note that the relative address is 0x3A when writing in compensation.
The response in the case of being written in normally is the same as request.
* In function code 06, be sure to write in a 16-bit integer data after address 40057. (If the start
address specifies a 32-bit integer data area, an error response will be returned.)
[Request]
Function
1 byte
0x06
Start address
2 bytes
0x0000 to 0xFFFF
Output data
2 bytes
[Response]
Function
1 byte
0x06
Start address
2 bytes
0x0000 to 0xFFFF
Output data
2 bytes
[Error response]
Error code
1 byte
0x86 (Fu0x80)
Exception code
1 byte
01 or 02 or 03
[Request]
Function
06
[Response]
Function
06
Start address (HI)
00
Start address (HI)
00
Start address (LO)
3A
Start address (LO)
3A
Compensation (HI)
00
Compensation (HI)
00
Compensation (LO)
14
Compensation (LO)
14