![Unipower ARE-M02406 Product Manual Download Page 46](http://html1.mh-extra.com/html/unipower/are-m02406/are-m02406_product-manual_3893790046.webp)
Micro
ARE-M Series 24V Chargers, Single Phase
Setup and Operation
PM990-1070-24, Issue 12
4-11
Change Float Voltage
Float = 26.4V
Very Low Voltage Alarm (VLVA)
Set the VLVA alarm to a voltage that, if charger output voltage falls below this setting, an alarm will be
annunciated.
High Battery Temperature Alarm (HBTA)
Set the HBTA alarm to a temperature that, if the battery temperature rises above this setting, an alarm will
be annunciated. The temperature compensation (option 2) must be purchased and installed in order for
this alarm to work. If this option is installed the battery temperature can be found in the “Battery
Temperature” menu as shown in Fig. 4-2.
Rectifier Fail Alarm (RECTF)
Gives a RECTF alarm, if enabled, if both an alarm that can cause a rectifier failure alarm (RECT) is
enabled and the alarm is active.
AC Fail Alarm (ACF)
Gives an ACF fail alarm when the AC power to the charger is missing.
Alarm Mode Latching
In the enable mode this allows alarms to be latched in the alarm state until an operator clears them by
pressing any key on the key pad. In the disable mode, the alarms clear once the alarm condition has
cleared.
Set Parameter Values
Parameter values accessed from the
System Setpoints
,
System Alarms
, and
Summary Alarm
screens
are changed as follows.
1.
From the
Home
screen press UP or DN until CHARGER SETUP appears. Press SEL.
2.
From the
System Setpoints
screen, press one of the following:
•
Press SEL to set system set point parameters.
•
Press UP or DN to move to another screen in the
Setup Select Screens
column. Then press SEL.
3.
If a parameter screen appears, see example at right, go to step 5.
If the
Enter Password
screen appears, go to step 4.
4.
At the
Enter Password
screen, press UP until your password
appears and then press SEL. Go to step 5.
5.
At the parameter screen, press UP or DN to display the parameter to be changed. Press SEL.
•
If changing a parameter value, the on-screen equals sign (=) will flash. Go to step 6.
•
To change Alarm Delays, again press SEL and go the step 6.
6.
Press UP or DN until the desired value (e.g. set point voltage or current, enable/disable, or alarm
delay time) is displayed. Press one of the following:
•
Press SEL to store the new value. The equals sign will stop flashing.
•
Press ESC to cancel or abort changes.
7.
Press UP or DN to move vertically to the next value to be changed.