Micro
ARE-M Series 24V Chargers, Single Phase
Setup and Operation
PM990-1070-24, Issue 12
4-8
will be toggled on and off. This test will produce an audible clicking as the relays are switched. The AC
fail relay is not toggled.
1.
At the Home screen press UP or DN until OPERATING MODE appears. See Figure 4-3.
2.
Press SEL. The present operating mode will be displayed.
3.
Press DN. If the
RELAY/LAMP TEST
screen appears, go to step 5. If the
Enter Password
screen
appears, go to step 4.
4.
At the
Enter Password
screen, press UP until your password is displayed and then press SEL. Go to
step 5.
5.
Press SEL to begin the test. Testing will continue until ESC is pressed.
6.
Press ESC to step back up through the menu hierarchy to the
Home
screen.
4.3.4 Change Charger Setup (Configuration)
A default setup (i.e. configuration) is factory-installed. Table 4-1 lists the factory parameter values.
Customer parameter values can be loaded if supplied with the order for the charger.
Refer to the menu shown in Figure 4-4 when setting-up a newly installed charger or when changing the
setup of an operating charger. The figure shows how to navigate the
Charger Setup
menu so that you can
change operating parameters to accommodate your application.
Note:
If password protection is enabled, only authorized personnel will be able to change setup parameter
values. When changing multiple values, you will be asked for your password only once during a charger
setup session.
TABLE 4-1 FACTORY DEFAULT SETUP PARAMETER VALUES
Parameter
Factory Default
Operating Mode (FL/EQ)
Float
Float Setpoint
26.4V
Equalization (EQ)
28.0V
Low Voltage Alarm (LVA)
24.0V
Very Low Voltage Alarm (VLVA)
23.3V
High Voltage Alarm (HVA)
29.0V
High Voltage Shutdown (HVSD)
30.0V
Low Current Alarm (NCA/LCA)
2% of rating
Current Limit (CL)
110% of rating
High Battery Temperture (HBTA)
35
°
C
Temperature Compensation
Disabled
AC Fail Equalize
Disabled
Periodic Equalize
Disabled
Load Share
Disabled
Some parameters are dependent upon optional features. For example, temperature compensation requires
the installation of an optional temperature sensor. Before setting up a charger, refer to Table 1-1 Model
Designation and determine which options are installed in the charger at hand.
The procedures in this section are a bit more detailed than in the preceding sections. Consequently,
several subsections are employed to simplify describing of the setup options available within this menu.