Micro
ARE-M Series 24V Chargers, Single Phase
Installation
PM990-1070-24, Issue 12
2-5
2.3
MECHANICAL INSTALLATION
Install the charger in a location that provides:
•
A dry, well ventilated, vibration-free environment with temperature and humidity limits as stated in
Section 1.3 Specifications
•
Sufficient access for installation and servicing
•
Sufficient ceiling height to permit use of overhead cable trays for distribution wiring
•
A level, flat floor or a wall capable of supporting the weight of the charger and accepting anchoring
bolts
•
A non-combustible surface beneath the charger
•
A pest and varmint free area
Charger dimensions are stated in the Section 1.3 Specifications and shown in Figures 2-1 and 2-2.
Charger weight is provided in the Specifications section.
The mounting method (floor, rack, or wall) is usually specified on the order so the necessary brackets are
installed on the charger at the factory. Charger wall mounting hardware (1/4-20 screws, lock washers and
nuts), rack mounting hardware (12-24 screw and nuts) or floor mount hardware (3/8 bolts and anchors) is
customer supplied since it must be selected on-site to be appropriate for the mounting surface.
Figures 2-1 and 2-2 show charger mounting bracket locations. Charger mounting options are listed below.
•
A 12" or 24" cabinet can be mounted in a 19" rack using the supplied rack angle brackets; the wide
bracket option is required for a 23" rack
•
All cabinets can be fastened to a wall using the supplied rack angle brackets fastened to rear of
cabinet
•
All cabinets can be free standing on a solid or elevated floor; optional floor mounting brackets are
required
CAUTION
Charger models that output 24 Vdc @ 50A or 100A
can have hot cabinet surfaces. Install these models
so that top and rear cabinet surfaces are unlikely to
be touched by personnel.
Charger models with drip shields are to be placed
where the shield is unlikely be in contact with
people. The shield should not have anything set
upon it.
ATTENTION
La surface des cabinets peut être CHAUDE pour
les modèles de chargeur avec une sortie de 24 Vdc
@ 50A ou 100A. Installez ces modèles dans un
endroit ou ils sont peu susceptibles d'être touchés
par le personnel.
Les modèles avec un « pare-gouttes » doivent être
placées là le dessus est peu probable d'être en
contact avec du personnel. Ne rien placer sur le
pare-gouttes.