![Unipower ARE-M02406 Product Manual Download Page 42](http://html1.mh-extra.com/html/unipower/are-m02406/are-m02406_product-manual_3893790042.webp)
Micro
ARE-M Series 24V Chargers, Single Phase
Setup and Operation
PM990-1070-24, Issue 12
4-7
4.3.3 Change Operating Mode (Manual Equalization)
Use this series of screens to manually enable and terminate equalization.
Note:
If password protection is enabled, only authorized personnel will be able to change the operating
mode.
To enable equalization:
1.
At the
Home
screen press UP or DN until OPERATING MODE appears. See Figure 4-3.
2.
Press SEL. The
Equalize Mode
screen will appear.
3.
Press SEL. If the
Begin Equalize
screen appears, go to step 5. If
the
Enter Password
screen appears, go to step 4.
4.
At the
Enter Password
screen, press UP until your password is displayed and then press SEL. Go to
step 5.
5.
At the
Begin Equalize
screen, press one of the following:
•
Press SEL to select equalize mode. Go to step 6.
•
Press ESC to remain in float mode. Go to step 7.
•
Pressing UP or DN displays the
Stay in Float Mode
screen; press SEL to stay in float mode. Go
to step 7.
6.
At the
Equalize Duration
screen, press UP or DN to set the duration (1-255 hours or Always On).
Press SEL to store the time.
7.
Press ESC to step back up through the menu hierarchy to the
Home
screen.
To terminate equalization and return to float mode:
1.
At the
Home
screen, press UP or DN until OPERATING MODE
appears.
2.
Press SEL. If the
Equalize Mode
screen at right appears, go to step
4. If the
Enter Password
screen appears, go to step 3.
3.
At the
Enter Password
screen, press UP until your password is
displayed and then press SEL. Go to step 4.
4.
At the
Equalize Mode
screen, press one of the following:
•
Press SEL to terminate (cancel) equalization and go to float mode; go to step 5.
•
Press ESC to stay in equalize mode. Go to step 5.
•
Pressing UP or DN displays the
Stay in Equalize Mode
screen; press SEL to stay in equalize
mode. Go to step 5.
5.
Press ESC to step back up through the menu hierarchy to the
Home
screen.
4.3.4.1
Alarm Relay/Lamp Test
This series of screens is used to test the alarm relays and Alarm LED. Since the alarm relays are being
toggled (de-activated and activated),
any attached annunciator (e.g. horn, siren, electronic messaging)
²
See section 2.4.6 for the relay state for "NORMAL CONDITION" and "ALARM CONDITION".
EQUALIZE MODE
SEL to terminate
28.0VDC 1.7ADC
Man. Equalize 24hrs left
EQUALIZE MODE
SEL to activate