How to interpret the burner’s “Performance curve”
To check if the burner is suitable for the boiler to which it must be installled, the following parameters are needed:
furnace input, in kW or kcal/h (kW = kcal/h / 860);
backpressure (data are available on the boiler’s ID plate or in the user’s manual).
Example:
Furnace input: 600kW
Backpressure: 4mbar
In the “Performance curve” diagram (Fig. 2), draw a vertical line matching the furnace input value and an horizontal line matching the
backpressure value. The burner is suitable if the intersection point A is inside the performance curve.
Fig. 2
Data are referred to standard conditions: atmospheric pressure at 1013mbar, ambient temperature at 15°C
Burner model identification
Burners are identified by burner type and model. Burner model identification is described as follows.
Type
RG1025
Model
G-. PR. S.
*
. A.
(1) (2) (3) (4) (5) (6)
(1) BURNER TYPE
RG1025 - RG1030 - RG1040
(2) FUEL
G - Light oil
(3) OPERATION
(Available versions)
PR - Progressive
MD - Fully modulating
(4) BLAST TUBE
S - Standard
(5) DESTINATION COUNTRY
* - see data plate
(6) BURNER VERSION
A - Standard Y - Special
Campo di lavoro bruciatori
Tipo P60 Mod. M-xx.x.IT.A.0.50 - M-.xx.x.IT.A.0.65
-1
0
1
2
3
4
5
6
7
8
100
200
300
400
500
600
700
800
900
Potenza kW
Contropressione in camera di
combustione mbar
A
Summary of Contents for RG1025
Page 2: ......
Page 18: ...C I B UNIGAS M039144CD 18 BERGONZO NOZZLES Fig 15 ...
Page 19: ...C I B UNIGAS M039144CD 19 Fig 16 ...
Page 20: ...C I B UNIGAS M039144CD 20 Fig 17 ...
Page 21: ...C I B UNIGAS M039144CD 21 Fig 18 ...
Page 38: ......
Page 39: ......