Adjusting the combustion head
To let the burner operate at a lower output, loose the
VB
screw and move progressively back the combustion head towards the MIN
position, by turning clockwise the
VRT
ring nut. Fasten
VB
screw when the adjustment is accomplished.
Calibration of air pressure switch
To calibrate the air pressure switch, proceed as follows:
Remove the transparent plastic cap.
Once air and gas setting have been accomplished, startup the burner.
During the pre-purge phase o the operation, turn slowly the adjusting ring nut
VR
in the
clockwise direction until the burner lockout, then read the value on the pressure switch scale
and set it to a value reduced by 15%.
Repeat the ignition cycle of the burner and check it runs properly.
Refit the transparent plastic cover on the pressure switch.
“MAX”
head position
head position
VB
VRT
VR