background image

42

Reset / manual lockout

The system can be manually locked by simultaneously pressing the 

ENTER (InFo) 

button and 

any other button 

on the AZL2.... This

function allows the user to stop the system from the operating level should an emergency occur. When making a reset, the following
actions are carried out:

Alarm relay and the fault display are off

the lockout position is cancelled

the unit performs a reset, then it switches to stand-by

If the unit is in the lockout position, a reset can be made by pressing the 

InFo 

button for 1…3 seconds. The function is available only

when the unit is in the lockout position. Longer or shorter pushes on the button do not produce a reset so that the system maintains the
lockout position.

Timeout for menu operation

The time for automatically leaving the parameter setting level can be adjusted between 10 and 120 minutes, using the  parameter 127
(Timeout for menu operation). If, during that period of time, there is no operation via the AZL2..., the parameter setting level is quit and
the password level reset to 

Info / Service

.

Caution! In addition, this timeout or interruption of communication between the LMV2.. and the AZL2... during the time the
curves are set leads to lockout!

Codice errore / Error code Codice diagnostico / Diagnostic code

Descrizione / Meaning

167

2

  / Manual lockout via AZL2…

Codice erroreC Error code

Codice diagnostico Diagnostic code

DescrizioneMeaning

167

8

 Manual locking

Summary of Contents for G225X

Page 1: ...M039642CA 0 2 03 2023 BURNERS BRUCIATORI BRULERS BRENNER QUEMADORES Microprocessor controlled MANUAL OF INSTALLATION USE MAINTENANCE LMV 2x 3x Gas burners G225X G270X G325X...

Page 2: ...nufacturer declines all responsibility for non compliance with this manual Personnel training The user is the person organisation or company that has acquired the appliance and intends to use it for t...

Page 3: ...compliance with the regulations in force GENERAL INSTRUCTIONS DEPENDING ON FUEL USED ELECTRICAL CONNECTION For safety reasons the unit must be efficiently earthed and installed as required by current...

Page 4: ...azard Do not use the burner in situations other than the ones provi ded for in the data plate Do not use fuels other than the ones stated Do not use the burner in potentially explosive environments Do...

Page 5: ...burner performance by controlling the flame geometry and combustion efficiency Fuel and air are routed through separated channels inside the combustion head then mixed to ignite the flame inside the c...

Page 6: ...RNER TYPE G225X M G270X M G325X M G225X L G270X L G325X L Output min max kW 230 2250 340 2700 620 3250 230 2250 340 2700 620 3250 Fuel Natural gas I3B P Category see next paragraph Gas rate Natural ga...

Page 7: ...Group AL AT BE BG CH CY DE DK EE ES FI FR GB GR HR HU IE IS IT LT LU LV MK MT NO NL PL PT RO SE SI SK TR H L E 2R EK Er LL E R DANGER The burner must be used only with the fuel specified in the burner...

Page 8: ...636 487 845 292 80 579 132 1393 1002 687 538 875 310 100 592 145 1476 1085 791 642 942 353 G270X 50 1401 1501 550 100 1021 1251 725 526 450 533 384 624 190 65 564 117 1497 971 447 636 487 845 292 80...

Page 9: ...burner s gas valve Then subtract the backpressure The result is called pgas Draw a vertical line matching the furnace input value 600kW in the example quoted on the x axis as far as intercepitng the...

Page 10: ...d it depends only on gas flow provided combustion is properly adjusted flue gases residual O2 percentage complies with Recommended combustion values table and CO in the standard limits During this sta...

Page 11: ...he pressure rate curves showed on the next paragraph it is easy to find out the burner s output in Stm3 h quoted on the x axis from the pressure measured in the combu stion head quoted on the y axis T...

Page 12: ...whose dimensions are GxX series 1600mm x 1000mm x 860 mm L x P x H Such packages fear moisture and are not suitable for stacking Packing cases of this type are affected by humidity and are not suitab...

Page 13: ...agram In case the burner must be coupled with boilers with a combustion chamber smaller in dia meter or shorter than those described in the diagram please contact the supplier to verify that a correct...

Page 14: ...diagrams are in compliance with the current laws Gas train with valves group VGD and MBE with built in gas pressure governor gas leakage pressure switch PGCP Legend WARNING before executing the conne...

Page 15: ...B DLE 10 Manual valve optional MULTIBLOC DUNGS MB DLE 405 412 MB DLE 415 420 Mounting 1 Mount flange onto tube lines use appropriate sealing agent 2 Insert MB DLE note position of O rings 3 Remove Mul...

Page 16: ...allation the output pressure must be monitoried by min and max pressure switches set to 20 of the setpoint 2 Mounting on pipe Sensor position 5x DN according to MBE Pipe fitting with female thread siz...

Page 17: ...e vertical WARNING removing the four screws BS causes the device to be unserviceable SA SA TP D BS SKP1 SKP2 SIEMENS VGD Mounting positions TP Siemens VGD con SKPx Example of gas train Gas filter T VR...

Page 18: ...ct the gas valves group and pressure switches plugs Overall dimensions mm BURNERS WITH INVERTER VARIANT if provided ATTENTION it is reccomended to install the filter with gas flow parallel to the floo...

Page 19: ...etting of the burner also allows a saving on the consumption of the fan engine Terminal interface with Inverter Input signals for the inverter depending on the equipment LMV51 300 LMV52 xxx 4 20mA HAG...

Page 20: ...ve parts i e fuel feeding pipes metal structures to connect the burner to ground In connecting the supply wires to the burner MA terminal strip ensure that the earth wire is longer than the phase and...

Page 21: ...onfiguration with separate electrical panel optional The length of the electrical cables must comply with the provisions in the technical sheets of the equipment or the advice the company gives at the...

Page 22: ...ING WITH THESE E G DISCONNECTION EVEN PARTIAL OF THE ELECTRICAL LEADS OPENING THE GENERATOR DOOR DISMANTLING OF PART OF THE BURNER NEVER OPEN OR DISMANTLE ANY COMPONENT OF THE MACHINE EXCEPT FOR ITS M...

Page 23: ...by the light B2 on see front panel At the end of the pre purge the air damper is driven to the ignition position the ignition transformer is energised signalled by the light B4 on the front panel then...

Page 24: ...t therefore ventilate the rooms and wait long enough for the gases to dissipate out side before switching on Attention if it is necessary to change the head position repeat the air and fuel adjustment...

Page 25: ...Info mode 3 Parametere setting mode 4 Plant heat request 5 Oil pre heater energised 6 Fan motor energised 7 Ignition transformers energised 8 Open valves 9 Flame 10 Lock unlock codes 11 Closing actua...

Page 26: ...TSA1 primo tempo sicurezza trasformatore accensione ON TSA1 1st safety time ignition transformer ON Ph42 TSA1 primo tempo sicurezza trasformatore accensione OFF TSA1 1st safety time ignition transform...

Page 27: ...ome basic parameters as 5 Example choose parameter 102 to show the date the display shows parameter 102 flashing on the left and characters _ _ on the right 6 press InFo for 1 3 seconds the date will...

Page 28: ...and find out the fault in the Error table To perform the reset press InFo for one second The unit displays an event which does not lead to shutdown The display shows current error code c alternating...

Page 29: ...outs History see chapter 23 in the LMV2x manual Adjusting the gas valves group Multibloc MB DLE The multibloc unit is a compact unit consisting of two valves gas pressure switch pres sure stabilizer...

Page 30: ...es 9 Output flange 10 Test point connection M4 downstream of valve 2 11 Gas flow direction 12 Test connection G 1 8 downstream of valve 1 on both sides 13 Vent nozzle pressure regulator 14 Filter belo...

Page 31: ...nts do not exceed a value that creates a hazardous condition to the burner Adjusting output pressure for positive pressure systems requires PS 10 40 or PS 50 200 Outlet pressure MIN 10 25 50 75 MAX PS...

Page 32: ...cording to its mounting position remove the pressure switch plastic cover if the maximum pressure switch is mounted upstreaam the gas valves measure the gas pressure in the network when flame is off b...

Page 33: ...wise the knob VRT Fasten VB screw when the adjustment is accomplished Depending on the boiler application it is possible to act on the holes figure B to improve the flame stability and NOx CO emission...

Page 34: ...the combustion head Examine and clean the ignition electrodes adjust and replace them if necessary Examine and clean the detection electrode photoelement according to the burner models replace it if...

Page 35: ...ce as high compared to the last check You can change the filter without removing the fitting 1 Interrupt the gas supply closing the on off valve 2 Remove screws 1 4 using the Allen key n 3 and remove...

Page 36: ...ntact metallic parts blast tube head etc other wise the boiler s operation would be compromised Check the electrodes position after any intervention on the combustion head C G AR V C G A O VR Key VRT...

Page 37: ...iler s operation would be compromised Check the electrodes position after any intervention on the combustion head EA ER 6 6 60 2 3 mm EA Ignition electrode ER Detection electrode 0 1 2 3 4 5 6 7 35 34...

Page 38: ...her to finish using the burner or replacing and disposing of it based on the actual state of the appliance and any repair costs The use of the burner for other purposes after the expiry of the terms o...

Page 39: ...witch functions and links Burner control damaged Replace burner control BURNER LOCKS OUT WITHOUT ANY GAS FLOW Gas valves don t open Check voltage on valves if necessary replace valve or the burner con...

Page 40: ...a L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail cibunigas cibunigas it Note specifications and data subject to change Errors an...

Page 41: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...

Page 42: ...900 Process data 32 Actuators references 33 Gas proving system 33 Air fuel curve points 33 COMMISSIONING THE BURNER 34 Warm setting 38 Cold setting 39 BURNER STARTUP WITH LMV2x ALREADY PROGRAMMED 40...

Page 43: ...CTIONS FOR BURNERS z The burner should be installed in a suitable room with ventilation openings complying with the requirements of the regulations in force and sufficient for good combustion z Only b...

Page 44: ...ditions such as the development of toxic or explosive mixtures DIRECTIVES AND STANDARDS Gas burners European directives Directive 2009 142 EC Gas Appliances Directive 2006 95 EC on low voltage Directi...

Page 45: ...apparatus EN 50165 Electrical equipment of non electric appliances for household and similar purposes Safety requirements UNI EN 746 2 Industrial thermoprocessing equipment Burner data plate For the...

Page 46: ...forms all the burner control functions and of the Siemens AZL local programming unit that interfaces the system with the user Keys 1 Burner 2 AZL2 3 Air actuator 4 Fuel actuator 5 LMV2 User interface...

Page 47: ...ice mode Info and Enter keys Used for Info and Service menues Used as Enter key in the setting modes Used as Reset key in the burner operation mode Used to enter a lower level menu Key Used to decreas...

Page 48: ...8 Parameters level heating engineer...

Page 49: ...ription Password 000 Internal parameters OEM Service 100 Informazioni generali General OEM Service Info 200 Controllo bruciatore Burner control OEM Service 300 Controllo bruciatore solo LMV26 Burner c...

Page 50: ...kup data set Service Info Param Descrizione Description Password LMV20 LMV27 LMV26 LMV37 102 Data produzione in gg mm aa Identification date yy mm dd Service Info x x x 103 Numero identificativ Identi...

Page 51: ...ed OEM Service x x 145 Indirizzo dispositivo per Modbus Device address for Modbus OEM Service x x 146 Velocit di trasmissione per Modbus Baud rate for Modbus OEM Service x x 147 Parit per Modbus Parit...

Page 52: ...erci zio azzerabile da Service Fuel 1 Operation hours resettable Service Info x 174 Fuel 1 secondo combustibile Numero di partenze azzerabile da Service Fuel 1 Number of startups resettable Service In...

Page 53: ...e fuel train modula ting multistage actuators etc __ undefined delete curves 1 gas direct ignition G mod 2 ignition by gas pilot connected between the two gas solenoid valves EV1 EV2 Gp1 mod 3 ignitio...

Page 54: ...x x x 210 Allarme impedimento avviamento 0 non attivo 1 attivo Alarm in the event of start prevention 0 deactivated 1 activated OEM Service x x x 211 Tempo aumento giri ventilatore valore fab brica 2...

Page 55: ...nge impostazione 20s 60min Gas Prepurge time default value 20s range 20s 60min OEM Service x x x 226 Gas tempo di preaccensione valore fab brica 2s range impostazione 0 2s 60min Gas Preignition time d...

Page 56: ...ivo 1 esso modificabile solo su LMV37 Dal punto di vista della sicurezza il funzionamento continuo valido esclusiva mente per bruciatori di gas con elettrodo di rilevazione Gas Forced intermittent ope...

Page 57: ...Postpurge time 3 abortion with load controller LR ON OEM Service x x x 261 Olio sonda rilevazione fiamma attivo valore fabbrica 0 0 QRB QRC 1 ION QRA Oil active detector flame evaluation default value...

Page 58: ...0 inactive 1 active from phase 38 2 active from safety time TSA OEM Service x x 277 Olio Pressostato olio di massima ingresso POC 0 inattivo 1 pressostato olio di massima 2 POC Oil Pressure switch max...

Page 59: ...lvole EV1 EV2 del gas regolazione pneumatica Gp1 mod pneu 9 accensione tramite pilota gas con attacco a monte dell elettrovalvola EV1 del gas regolazione pneumatica Gp2 mod pneu 10 olio modulante con...

Page 60: ...ore fabbrica 1 0 QRB QRC 1 ION QRA Fuel 1 Gas active detector flame evalua tion default value 1 0 QRB QRC 1 ION QRA OEM Service x 322 Combustibile 1 Gas Preventilazione valore fabbrica 1 1 attivo 0 no...

Page 61: ...Intervallo 2 valore fabbrica 2s range impostazione 0 2s 60min Fuel 1 Gas Interval 2 default value 2s range 0 2s 60min OEM Service x 333 Combustibile 1 Gas Tempo postcombu stione valore fabbrica 8s ra...

Page 62: ...t filling time default value 3s range 0 2s 10s OEM x 345 Combustibile 1 Gas tempo test pressione gas valore fabbrica 10s range imposta zione 0 2s 60s Fuel 1 Gas proving test time gas pres sure default...

Page 63: ...mbustibile 1 Olio tempo di risposta a cadute di pressione entro TSA1 e TSA2 valore fabbrica 1 8s range imposta zione 0 2s 14 8s Fuel 1 Oil time to respond to pressure faults in TSA1 and TSA2 default v...

Page 64: ...censione corta Ph38 fase pro gramma 38 1 preaccensione lunga con ventilatore Ph22 fase programma 22 Fuel 1 Oil time oil ignition default value 1 0 short preignition Ph38 progr phase 38 1 long preignit...

Page 65: ...ting the cur ves OEM Service x x x 403 Curve controllo inverter F A si accede alla lista dei punti da impostare da P0 a P9 con sultare paragrafo Impostazione curve Ratio control curves VSD curve setti...

Page 66: ...repurge speed 100 Index 2 postpurge speed 50 OEM Service x x 504 Combustibile 1 Posizione servocomando combustibile in assenza di fiamma no flame Indice 0 posizione di sosta 0 Indice 1 posizione preve...

Page 67: ...di carico per modulazione valore fabbrica n d range imposta zione 20 100 Lower load limit default value n d range 20 100 OEM Service x x x 546 Percentuale massima di carico per modula zione valore fa...

Page 68: ...0 combustibile Indice 1 aria Tolerance limit of position monitoring 0 1 Index 0 fuel Index 1 air OEM Service x x x 608 Combustibile 1 Impostazione punto di riferi mento Indice 0 combustibile Indice 1...

Page 69: ...top SQN1 3 both OEM x 613 Tipo di servocomando Indice 0 combustibile Indice 1 aria 0 5s 90 1Nm 1 2Nm 3Nm 1 10s 90 6Nm 2 17s 90 10Nm Type of actuator Index 0 fuel Index 1 air 0 5 s 90 1Nm 1 2Nm 3Nm 1 1...

Page 70: ...tion of analog output default value 0 0 DC 0 10 V 1 DC 2 10 V 2 DC 0 2 10 V OEM Service LMV27 x x ATTENTION as for SQM3x actuators set the direction according to the acutator function As far as SQN1x...

Page 71: ...ror history 701 725 02 diagnostic code Service Info Storico errori 701 725 03 classe errore Error history 701 725 03 error class Service Info Storico errori 701 725 04 fase Error history 701 725 04 ph...

Page 72: ...Active load source OEM Service 945 Solo con LMV26 Combustibile attuale 0 combustibile 0 1 combustibile 1 Actual fuel 0 fuel 0 1 fuel 1 Service Info 947 Risultato interrogazione contatti codifica bit...

Page 73: ...a leakage test designed to detect leaking gas valves and if necessary to pre vent the valves from opening or ignition from being switched on Lockout is initiated When performing valve proving the gas...

Page 74: ...2x already programmed At the first LMV startup the AZL display will show It means that the unit was never set or that no mode was chisen or that some parameters have to be set furthert Push F fuel and...

Page 75: ...l elettrov EV1 del gas Gp2 mod 4 accensione a gasolio modul Lo mod 5 accens a gasolio bistadio Lo 2 stage 6 accens a gasolio tristadio Lo 3 stage Burner operating mode fuel train mod multi stage actua...

Page 76: ...e fuel actuator 0F until the requested value is reached for example 12 15 see below for the ignition point or press F and to decrease the angle To set the air damper opening angle 0A in the ignition p...

Page 77: ...er is operating warm setting by pressing the ENTER InFo or while the burner is in stand by mode cold setting by pressing ENTER CAUTION at the first burner adjustment it is recommended to set the maxim...

Page 78: ...ugh the flue analyser Keep the air excess inside normal figures from 3 to 7 residual O2 operating by means for the air damper servomotor Keep increasing the air damper opening and then the gas throttl...

Page 79: ...t before end by pressing ESC or for a faulty shutdown the message OFF UPr Start preven tion will be diplayed until all the curvepoints will be set Note2 if the gas flow rate at high flame point maximu...

Page 80: ...e than 5 seconds to process the curve downwards The curve is then a straight line go on checking the combustion values point by point change them if necessary and in case linearise the curve again Bef...

Page 81: ...e burntime Ph72 travelling to postpurging Ph74 postpurge countdown is displayed Press ESC the parameter 546 Setting the maximum load is displayed Then press to exit the programming mode The display wi...

Page 82: ...n Longer or shorter pushes on the button do not produce a reset so that the system maintains the lockout position Timeout for menu operation The time for automatically leaving the parameter setting le...

Page 83: ...levels By means of a proper use of the keys it is possible to enter the various level parameters as shown in the following flow chart The burner and consequently the LMV2x are factory set the air and...

Page 84: ...nd go back to the flashing number The Info level shows some basic parameters as 5 Example choose parameter 102 to show the date the display shows parameter 102 flashing on the left and characters _ _...

Page 85: ...h another message Diagnostic code in the example diagnostic code 3 Record the codes and find out the fault in the Error table To perform the reset press InFo for one second The unit displays an event...

Page 86: ...ht By pressinf or it is possible to scroll up down the parameter list 2 Once the last parameter is accessed 143 by pressing the End message will blink 3 Press InFo for more than three seconds or for m...

Page 87: ...ignition time OFF Ph44 t44 intervallo 1 t44 interval 1 Ph50 TSA2 secondo tempo sicurezza TSA2 2nd safety time Ph52 t52 intervallo 2 t52 interval 2 Ph60 Funzionamento 1 stazionario Operation 1 stationa...

Page 88: ...ess ENTER until the display will show with the button go to the group 000 of the parameters and press with the buttons and go to 050 parameter press the disply show press again with the button select...

Page 89: ...uttons by pressing enter to confirm iWith the buttons go to the group 000 of the parameters press end select the 050 parameter press the disply show with the button the display shows press again with...

Page 90: ...50 ERROR CODE TABLE...

Page 91: ...51...

Page 92: ...52...

Page 93: ...53...

Page 94: ...54...

Page 95: ...55...

Page 96: ...56...

Page 97: ...57...

Page 98: ...58...

Page 99: ...59...

Page 100: ...60...

Page 101: ...61...

Page 102: ...62...

Page 103: ...63...

Page 104: ...64...

Page 105: ...L PE QRB C N ION QRB C X75 1 X10 05 1 X10 06 1 X3 02 1 PLUFT FLAMME P L PE N L 2 3 L X5 03 1 X8 04 1 X8 02 1 X5 03 X10 05 X7 01 X8 04 X8 02 X75 X10 06 X3 02 X3 04 N PE L 1 1 1 1 1 1 1 1 1 QRA QRA QRA...

Page 106: ...66 Wiring variants for LMV27 2 Fuel meter input 1 Supply fuel meter ConnectorX75 ConnectorX5 02 ConnectionsPmax...

Page 107: ...tion speed output 2 GND signal reference 1 Controller input 4 20mA 5 Supply 4 Feedback signal 3 PWM Pulse Width Modulation speed output 2 GND signal reference 1 External supply 24V DC ConnectorX75 Con...

Page 108: ...dulation speed output 2 GND signal reference 1 Controller input 4 20mA 5 Supply ConnectorX75 ConnectorX64 ConnectorX74 2 Fuel meter input 1 Supply fuel meter ConnectorX5 02 Connections Pmax 4 Feedback...

Page 109: ......

Page 110: ......

Page 111: ......

Page 112: ...and data subject to change Errors and omissions excepted C I B UNIGAS S p A Via L Galvani 9 35011 Campodarsego PD ITALY Tel 39 049 9200944 Fax 39 049 9200945 9201269 web site www cibunigas it e mail...

Reviews: