PART II: INSTALLATION
16
MultiBloc MBE
Threaded train with MultiBloc MBE - Mounting
Mounting VD-R & PS-...
Siemens VGD20.. e VGD40..
Siemens VGD20.. and VGD40.. gas valves - with SKP2.. (pressure governor)
ATTENTION: once the gas train is mounted according, the gas proving test mus be performed, according to the
procedure set by the laws in force.
ATTENTION: it is recommended to mount filter and gas valves to avoid that extraneous material drops inside the
valves, during maintenance and cleaning operation of the filters (both the filters outside the valves group and the
ones built-in the gas valves).
WARNING: Slowly open the fuel cock to avoid breaking the pressure regulator.
Attention:
In the case of the MBE... valve, a pressure limit switch downstream of the safety valve is mandatory.
1. Gas pressure regulation is possible with VD-R and PS pressure sensor only.
WARNING! For US/CN installation, the
output pressure must be monitoried by min. and max. pressure switches set to +/- 20% of the setpoint.
2. Mounting on pipe. Sensor position: 5x DN according to MBE. Pipe fitting with female thread size ¼, mount sensor with
seal, observe torque.
3. The pressure sensor includes a vent limiter according to UL 353 and ANSI Z21.18/CSA 6.3. No venting required in loca-
tions where vent limiters are accepted by the jurisdiction.
4. Only PS pressure sensors specified by DUNGS are authorised to be connected to the VD-R‘s M12 interface.
5. Only PS cables specified by DUNGS are authorised to be used to connect the PS to the VD-R. Max. cable length 3 m.
GAS BRUCIATORE ø185
501939
PGMAX
PGCP
PGMI
EV1
EV2
S
EV2
EV1
PGMAX
PGMIN
VD-R
PGCP
VD-V
VD-V
VD-R
PS
PS pressure sensor
Gas filter
Example of gas train MBE
Actuator
VD-R
The actuator
VD-V
does not need any adjustment (funzione ON-OFF)
The actuator
VD-R
It must be combined with the
PS
sensor (include
regolatore di pressione)
The
PS sensor
chosen based on the necessary pressure (there are
3 models)
Actuator
VD-V
M12 x 5
VD-R + PS
Summary of Contents for G225X
Page 41: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 48: ...8 Parameters level heating engineer...
Page 90: ...50 ERROR CODE TABLE...
Page 91: ...51...
Page 92: ...52...
Page 93: ...53...
Page 94: ...54...
Page 95: ...55...
Page 96: ...56...
Page 97: ...57...
Page 98: ...58...
Page 99: ...59...
Page 100: ...60...
Page 101: ...61...
Page 102: ...62...
Page 103: ...63...
Page 104: ...64...
Page 109: ......
Page 110: ......
Page 111: ......