PART I: SPECIFICATIONS
9
How to read the burner “Performance curve”
To check if the burner is suitable for the boiler to which it must be install-
led, the following parameters are needed:
furnace input, in kW or kcal/h (kW = kcal/h/860);
backpressure (data are available on the boiler ID plate or in the
user’s manual).
Example:
Furnace input: 600kW
Backpressure: 4 mbar
In the “Performance curve” diagram, draw a vertical line matching the fur-
nace input value and an horizontal line matching the backpressure value.
The burner is suitable if the intersection point A is inside the performance
curve.
Data are referred to standard conditions: atmospheric pressure at 1013
mbar, ambient temperature at 15° C.
Checking the proper gas train size
Performance Curves
To check the proper gas train size, it is necessary to the available gas pres-
sure value upstream the burner’s gas valve. Then subtract the backpressure.
The result is called
pgas.
Draw a vertical line matching the furnace input
value (600kW, in the example), quoted on the x-axis, as far as intercepitng
the network pressure curve, according to the installed gas train (DN65, in the
example). From the interception point, draw an horizontal line as far as
matching, on the y-axis, the value of pressure necessary to get the reque-
sted furnace input. This value must be lower or equal to the
pgas
value, cal-
culated before.
Ba
ck pressu
re
mbar
[mbar]
G225X M-
Power [kW]
Back pressurembar
[m
bar]
G270X M-
G325X M-
Power [kW]
Power [kW]
Campo di lavoro bruciatori
Tipo P60 Mod. M-xx.x.IT.A.0.50 - M-.xx.x.IT.A.0.65
-1
0
1
2
3
4
5
6
7
8
100
200
300
400
500
600
700
800
900
Potenza kW
Contropressione in camera di
combustione mbar
A
backpre
ssur
e i
n
combust
ion chamb
e
r (mbar)
Power kW
0
5
10
15
20
25
100
200
300
400
500
600
700
800
900
Potenza / Output (kW)
Minima pressione gas in
rete / Minimum inlet gas
pressure (mbar)
Rp 2" (50)
DN65
Power kW
minimum gas pressure
in
the net
work m
bar
DN65
Summary of Contents for G225X
Page 41: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 48: ...8 Parameters level heating engineer...
Page 90: ...50 ERROR CODE TABLE...
Page 91: ...51...
Page 92: ...52...
Page 93: ...53...
Page 94: ...54...
Page 95: ...55...
Page 96: ...56...
Page 97: ...57...
Page 98: ...58...
Page 99: ...59...
Page 100: ...60...
Page 101: ...61...
Page 102: ...62...
Page 103: ...63...
Page 104: ...64...
Page 109: ......
Page 110: ......
Page 111: ......