PART IV: MAINTENANCE
34
At least once a year carry out the maintenance operations listed below. In the case of seasonal servicing, it is recommended to carry
out the maintenance at the end of each heating season; in the case of continuous operation the maintenance is carried out every 6
months.
ROUTINE MAINTENANCE
Check that the gas meter is not moving when the burner is off. In case it is rotating, look for possible leaks.
Check the cleaning condition of the vent. Clean the vent by using exclusively a dry brush. If needed, disassemble it from the
motor’s shaft and wash it by using non corrosive detergents. Prior to disassemble the vent, take the measurements in relation to
the motor's shaft, so as to reassemble it in the same position.
Check that all parts in contact with combustive air (air box, protection mesh and Archimedean screw) are clean and free from any
obstruction that might impede free afflux. Clean it with compressed air if available and/or a dry brush or cloths. Eventually wash it
with non corrosive detergents.
Check the blast tube; it must be substituted in case of obvious cracks or anomalous holes. Slight deformations that do not affect
combustion may be tolerated
Check the condition of the burner-boiler gasket. Eventually substitute it.
Check the fan’s motor: no specific maintenance is needed. In case of anomalous noises when running, check the condition of the
bearings and eventually substitute them or completely substitute the motor.
Clean and examine the gas filter cartridge and replace it if necesssary;
Remove and clean the combustion head;
Examine and clean the ignition electrodes, adjust and replace them if necessary;
Examine and clean the detection electrode/photoelement (according to the burner models), replace it if necessary, in case of
doubt, check the detection circuit, after the burner start-up;
Clean and grease leverages and rotating parts.
Gas filter maintenance
Adjusting the gas valves group and removing the filter
WARNING: ALL OPERATIONS ON THE BURNER MUST BE CARRIED OUT WITH THE MAINS DISCONNECTED
AND THE FUEL MANAUL CUTOFF VALVES CLOSED!
ATTENTION: READ CAREFULLY THE “WARNINGS” CHAPTER AT THE BEGINNIG OF THIS MANUAL.
ATTENTION: when servicing, if it was necessary to disassemble the gas train parts, remember to execute the gas
proving test, once the gas train is reassembled, according to the procedure imposed by the law in force.
At least every 2 months, or more frequently depending on the case, clean the burner installation room.
Avoid leaving installations, papers, nylon bags, etc., inside the room. They could be sucked by the burner and cause mal-
functioning.
Check that the room’s vents are free from obstructions.
WARNING: Before opening the filter, close the manual cutoff valve downstream the filter and bleed the gas; check
that inside the filter there is no pressurised gas.
PART IV: MAINTENANCE
C
B
A
To clean or remove the filter, proceed as follows:
1 remove the cap unscrewing the fixing screws (A);
2 remove the filtering cartridge (B), clean it using water and soap, blow it
with compressed air(or replace it, if necessary)
3 replace the cartridge in its proper position taking care to place it
inbetween the guides as not to hamper the cap replacement;
4 be sure to replace the “O” ring into its place (C) and replace the cover
fastening by the proper screws (A).
Summary of Contents for G225X
Page 41: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 48: ...8 Parameters level heating engineer...
Page 90: ...50 ERROR CODE TABLE...
Page 91: ...51...
Page 92: ...52...
Page 93: ...53...
Page 94: ...54...
Page 95: ...55...
Page 96: ...56...
Page 97: ...57...
Page 98: ...58...
Page 99: ...59...
Page 100: ...60...
Page 101: ...61...
Page 102: ...62...
Page 103: ...63...
Page 104: ...64...
Page 109: ......
Page 110: ......
Page 111: ......