Unit
BAR
Imax
0.5 Amp
Rotat.
-->
Unit of measurement:
select the unit of measurement in BAR or PSI
Imax:
this parameter enables entry of the maximum current absorbed by the electric pump in routine
conditions, to enable shut-down of the motor in the event of excessive absorption. The motor is also shut down
if the current read during operation is below 0.5 A following interruption of the connection between the motor
and
the inverter. The trip time of the current overload safety device is inversely proportional to the entity of the
overload in progress; therefore a slight overload will lead to a more delayed trip time while a more significant
overload will accelerate the trip time. On activation of the device, if the Imax parameter is set at 0.5 A (factory setting), the display
automatically shows the settings page of the maximum current and no action is permitted until the absorption limit value is set.
Rotation direction:
this screen enables the user to invert the direction of rotation of the electric pump without
modification to the electric motor wiring. To modify the direction of rotation of the motor, use buttons "+" and
"-"; the direction indicated by the arrow has a purely indicative value and does not reflect the actual sense of
rotation which must be verified by the installer.
ADVANCED PARAMETERS:
The advanced parameters are accessible only to the technical assistance service. For access to these parameters, it is necessary to contact the
re-seller, a technical assistance centre or the manufacturer.
The following table lists the advanced parameters for reference when technical assistance is required.
REF.
PARAMETER
DESCRIPTION
1.2
Minimum frequency
Minimum motor start-up frequency
1.3
Stop frequency
Motor shutdown frequency
1.4
Nominal motor frequency
Maximum nominal motor frequency
1.5
Switching frequency
PWM Switching frequency
1.6
Frequency correction
Maximum frequency correction
1.7
Soft-start
Soft-start activation/deactivation
2.0
Flow switch activation
Flow switch activation or deactivation
2.1
Command source
Source of manual or automatic command
2.2
Auxiliary contact function
Selection of auxiliary contact function
2.3
I/O board input function
Function of I/O auxiliary board input contact
2.4
I/O board output function
Function of I/O auxiliary board output contact
2.5
Delay on stop
Delay on shutdown after closure of utilities
2.6
Autoreset interval
Time interval between autoreset attempts
2.7
No. autoreset tests
Number of autoreset attempts
2.8
Total automatic reset
Enabling of overall reset of all alarms
3.0
Pressure calibration 0.0 Bar
To carry out calibration of the pressure sensor at 0 Bar
3.1
Pressure calibration 5.0 Bar
To carry out calibration of the pressure sensor at 5 Bar
3.2
Flow sensor calibration
To carry out calibration of the flow sensor
3.3
Pressure test
Current pressure test signal
3.4
Flow switch test
Flow switch test signal
3.5
Software Release
Release of software
3.6
Power supply timing
Inverter power supply timer
3.7
Pump timing
Electric pump operational timer
3.8
Last error
Last error occurred log
3.9
Start-up
Pump start-up counter
4.0
Vboost
Voltage boost at 0Hz
4.1
Dry run
Time delay before activation of the protection due to no water
4.2
Protection starts per hour
Activation or deactivation of the control on the number of start-ups per hour (leak
checks)
4.3
Anti-blockage protection
Activation or deactivation of a function that automatically starts up the pump after 24
hours of disuse
4.4
Dead time PWM
Dead time PWM setting
4.5
Ki
PID controller integral constant
4.6
Kp
PID controller proportional constant
4.7
Boost time
Boost time at maximum frequency with soft start disabled
5.0
Ta max
Maximum ambient temperature
5.1
Tm max
IGBT module maximum temperature
5.2
Ta reduction index
Frequency reduction index on ambient temperature
5.3
Tm reduction index
Frequency reduction index on module temperature
5.6
Minimum voltage
Minimum power supply voltage threshold
5.7
Maximum voltage
Maximum power supply voltage threshold
5.9
Debug Variable
Debug variable selection for process value display