OPTIONAL AUTOMATIC VENT CONTROLLER

SECTION 5

THIS UNIT MUST BE INSTALLED BY A QUALIFIED ELECTRICIAN TO THE 17th EDITION BS7671 
REQUIREMENTS FOR ELECTRICAL INSTALLATIONS

1. Remove the front panel by loosening the retaining screws.

2. Screw the back box to the surface of a masonry wall in the 
conservatory, at the usual height of a wall switch.

3. Choose appropriate knock out for cable entry and smooth edges 
to prevent damage to cable insulation.

4. In any situation where the mains cable is not plastered into the 
wall, the cable must be adequately secured as close as possible to 
the control box to prevent undue stress on the cable.

5. Connect the cables in accordance with the wiring diagram, 
bringing sheath as close as possible to the terminal blocks, to 
prevent contact of the inner insulation with other parts of the p.c.b. 
Note that a junction box will be required in the ridge, to bring all the 
actuator cables together. Run a single four-core cable from here 
to the control box. Note that a fused isolator must be installed, 
providing a contact separation of at least 3mm in all poles.

6. Replace the front panel.

THIS UNIT TO BE INSTALLED USING BASEC OR HAR APPROVED CABLE, AND MUST BE SUITABLY EARTHED 

NOTE: CABLE NOT SUPPLIED BY ULTRAFRAME

SECTION 5

INSTALLATION OF VENT CONTROLLER

The Automatic Vent Controller is an integrated electronic 
thermostat and controller with rain sensor, for automatic and 
manual operation of motorised roof vents. The vents open 
automatically at high temperatures and close again when 
the temperature drops or rain is detected. Up to 6 Ultraframe 
actuators can be controlled by type Q8750.

TECHNICAL SPECIFICATION

Mains Supply: 

230V 5A 50Hz

Output current to actuators: 

5.2A max at 20% duty cycle

Opening impulse: 

Variable, 3 to 9 sec approx.

Closing impulse: 

11 sec approx

Di

ff

  erential temp of thermostat: 

2°C

Mounting angle of rain sensor: 

15° to 45°

Cable for rain sensor:

 0.5mm2 2 core round 

fl

 exible cable. Ø5 to 

7mm

Working voltage of rain sensor: 

1V to 6V wet - 7.5V to 10V dry 

(a.c.)

Equivalent resistance of rain sensor: 

Less than 80k ohms wet. 

Greater than 300k ohms dry

Finish: 

White only

Dimensions of controller: 

148 x 88 x 52 excluding thermostat 

setting knob

Dimensions of rain sensor: 

75 x 51 x 28 excluding cable gland

Weight of combined units in packing carton:

 450g

NOTE: CABLE NOT SUPPLIED BY ULTRAFRAME

Summary of Contents for ROOF VENT

Page 1: ...V2 August 2019 ROOF VENT INSTALLATION GUIDE...

Page 2: ...NICAL SUPPORT Tel 01200 452918 Email techsupport ultraframe co uk Please read in conjunction with the installation guide provided with the roof itself SECTION 1 PVCU ROOF VENT INSTALLATION GUIDE COMPO...

Page 3: ...above and ensure the tape is directed against section 2 1 SECTION 3 Run a bead of appropriate sealant ensuring a continuous run along the external upper muntin bar Please see section view for bead pos...

Page 4: ...rnal lower muntin bar knock into place The lower muntin may need supporting from underneath whilst secured into final postion 12 Whenthesealantonthemainframehascured re fit the outer sash by holding v...

Page 5: ...ECTION 4 20 Finished mounted motor in situ 17 Using the nuts and bolts provided attach the motor bracket to the sash bracket taking care not to damage the glazed unit 18a 19 Fit provided securing bolt...

Page 6: ...east 3mm in all poles 6 Replace the front panel THIS UNIT TO BE INSTALLED USING BASEC OR HAR APPROVED CABLE AND MUST BE SUITABLY EARTHED NOTE CABLE NOT SUPPLIED BY ULTRAFRAME SECTION 5 INSTALLATION OF...

Page 7: ...ost rainfall comes from the South West This is therefore the preferred side of the roof for the rain sensor but check local conditions especially on the East Coast or on Mainland Europe 15 TO 45 PITCH...

Page 8: ...kept free of grease and sealing compound OPENING ADJUSTMENT Within the opening distance selected at the actuator the opening distance when opening automatically can be adjusted in the range 100 300mm...

Reviews: