background image

7

SECTION 6

SWITCH AND CONTROLLER WIRING

4. Attach the unit with the self-adhesive pad provided to a convenient exposed part of the roof, with the black sensing pattern uppermost. 
The cable can point towards the ridge, gutter, or to either side. The unit must slope at a gradient of at least 15º to enable excess water to run 
o

ff

 . Packing may be required on a lean-to roof to ensure this. Avoid shelter from overhanging eaves, especially if the conservatory is on the 

sheltered side of a taller building (house etc). In the UK the prevailing wind and most rainfall comes from the South-West. This is therefore the 
preferred side of the roof for the rain sensor, but check local conditions, especially on the East Coast or on Mainland Europe.

15° TO 45° PITCH

PACKING WHEN PITCH IS
LESS THAN 15°

Rain Sensor Mounting Position

INSTALLATION OF RAIN SENSOR

SECTION 7

1. Pass the cable through the cable gland, strip the cable ends and 
crimp on the terminals supplied.

2. Push the terminals on to the blades. Do not over tighten the 
nuts and screws, or the conductive pattern many be damaged by 
indentation.

NOTE: Round 3A mains cable must be used to ensure that the 
cable gland grips the cable and forms a waterproof seal. (This 
cable carries only 9V a.c. however).

3. Fit the bottom cover without sealing the joint

Summary of Contents for ROOF VENT

Page 1: ...V2 August 2019 ROOF VENT INSTALLATION GUIDE...

Page 2: ...NICAL SUPPORT Tel 01200 452918 Email techsupport ultraframe co uk Please read in conjunction with the installation guide provided with the roof itself SECTION 1 PVCU ROOF VENT INSTALLATION GUIDE COMPO...

Page 3: ...above and ensure the tape is directed against section 2 1 SECTION 3 Run a bead of appropriate sealant ensuring a continuous run along the external upper muntin bar Please see section view for bead pos...

Page 4: ...rnal lower muntin bar knock into place The lower muntin may need supporting from underneath whilst secured into final postion 12 Whenthesealantonthemainframehascured re fit the outer sash by holding v...

Page 5: ...ECTION 4 20 Finished mounted motor in situ 17 Using the nuts and bolts provided attach the motor bracket to the sash bracket taking care not to damage the glazed unit 18a 19 Fit provided securing bolt...

Page 6: ...east 3mm in all poles 6 Replace the front panel THIS UNIT TO BE INSTALLED USING BASEC OR HAR APPROVED CABLE AND MUST BE SUITABLY EARTHED NOTE CABLE NOT SUPPLIED BY ULTRAFRAME SECTION 5 INSTALLATION OF...

Page 7: ...ost rainfall comes from the South West This is therefore the preferred side of the roof for the rain sensor but check local conditions especially on the East Coast or on Mainland Europe 15 TO 45 PITCH...

Page 8: ...kept free of grease and sealing compound OPENING ADJUSTMENT Within the opening distance selected at the actuator the opening distance when opening automatically can be adjusted in the range 100 300mm...

Reviews: