SECTION 8

ADJUSTMENT AND TESTING

TESTING

1. When the installation is complete, insert the supply fuse and 
switch the isolator on. Note that the vents are likely to open or close 
on power-up.

2. First check for correct operation of the vents by use of the tactile 
open/close switches.

IT IS VITAL THAT WHEN THE VENTS ARE CLOSED FULLY, THEY 
ARE NOT TOO TIGHTLY CLOSED. 

3. In warmer weather, automatic operation can be checked by turning 
the thermostat up and down. Note that the vent should 

OPEN 

when 

turned to a low temperature and 

CLOSE 

when turned to a high 

temperature.

In cold weather i.e: below 10ºC in the conservatory, the thermostat 
element can be warmed up by using a hair dryer on a

 LOW 

heat 

setting. This should cause the vents to open. Turn the thermostat up 
to check that they close.

4. To test the rain sensor, the vents must 

fi

 rst be opened and clean 

water sprayed onto the rain sensor. The vents should close within a 
few seconds.

NOTE: a wet rain sensor will prevent automatic opening. If 
testing in actual rain, the surface of the sensor can be dried 
with clean kitchen tissue. Take care that the sensing surface is 
not scratched. It must also be kept free of grease and sealing 
compound.

OPENING ADJUSTMENT

Within the opening distance selected at the actuator, the opening distance when opening automatically can be adjusted in the range 100-
300mm by turning the control as required. See drawing of controller on page 5. 

This is not a “customer control”. 

It should be pre-set by the 

installing electrician if the customer requests it. 

Note that the opening distance is reduced by turning clockwise.

THERMOSTAT ADJUSTMENT

The adjustment range of the thermostat is 10º to 30ºC. Set the control 
knob to the temperature at which you want automatic operation of 
the vents. The vents will open whenever the temperature rises above 
your setting and re-close when it falls below this setting.

RAIN SENSOR

A rain sensor mounted on the roof will prevent automatic opening 
of the vents, and will cause them to re-close if it rains when they are 
already open.

MANUAL CONTROL

The tactile switches can be operated at any time to temporarily 
override the automatic actions of the controller. With these switches 
you can set the vents to any desired position. Press the “open” 
switch to open vent and press the “close” switch to close vent. Note 
that automatic operation will resume, commensurate with climatic 
conditions and the thermostat setting.

NOTE

1. Following a period of rain, the rain sensor will take some time to dry.
Whilst still wet, it will hold the vents closed, and immediately re-close 
them if opened by the tactile switch.
2. If you wish to leave the vents in any 

fi

 xed position, 

fi

 rst use the 

open/close tactile switch, then switch o

ff

  the electric supply at the 

isolator.

USE OF CONTROLLER

SECTION 9

Summary of Contents for ROOF VENT

Page 1: ...V2 August 2019 ROOF VENT INSTALLATION GUIDE...

Page 2: ...NICAL SUPPORT Tel 01200 452918 Email techsupport ultraframe co uk Please read in conjunction with the installation guide provided with the roof itself SECTION 1 PVCU ROOF VENT INSTALLATION GUIDE COMPO...

Page 3: ...above and ensure the tape is directed against section 2 1 SECTION 3 Run a bead of appropriate sealant ensuring a continuous run along the external upper muntin bar Please see section view for bead pos...

Page 4: ...rnal lower muntin bar knock into place The lower muntin may need supporting from underneath whilst secured into final postion 12 Whenthesealantonthemainframehascured re fit the outer sash by holding v...

Page 5: ...ECTION 4 20 Finished mounted motor in situ 17 Using the nuts and bolts provided attach the motor bracket to the sash bracket taking care not to damage the glazed unit 18a 19 Fit provided securing bolt...

Page 6: ...east 3mm in all poles 6 Replace the front panel THIS UNIT TO BE INSTALLED USING BASEC OR HAR APPROVED CABLE AND MUST BE SUITABLY EARTHED NOTE CABLE NOT SUPPLIED BY ULTRAFRAME SECTION 5 INSTALLATION OF...

Page 7: ...ost rainfall comes from the South West This is therefore the preferred side of the roof for the rain sensor but check local conditions especially on the East Coast or on Mainland Europe 15 TO 45 PITCH...

Page 8: ...kept free of grease and sealing compound OPENING ADJUSTMENT Within the opening distance selected at the actuator the opening distance when opening automatically can be adjusted in the range 100 300mm...

Reviews: