background image

 

NT 208D GB1

 

 

 

8 / 20

 

5

 

- CONVERTER ASSEMBLY 

 

 

Mechanical fittings  

 Use a location that offers preferential conditions for easy access and vision. 

 Avoid mounting on supports exposed to vibration. 

 Avoid extreme weather conditions and direct exposure to the sun. 

 Wall fitting is done by two M5 screws for industrial enclosures, or by using our  

support and fixing on a 2 ‘’ vertical tube with our Ex d version . 

 

 

Electrical connections

: Refer to the diagram on the previous page. 

 

 Power supply: Connectors BR 1 

– Use flexible cables with section 0.5 to 1.5 mm2. 

- The recommended source is DC, 10 to 30 Volts (60 V on option): 12 / 24 (48). 
- Any polarity will do. The required power is less than 2 Watt. 

The  source  may  also  be  A.C.  (9  to  18  Volts 

–  50/60  Hz) via  a  transformer  on  the 

mains. The other and best solution is to order MiniSonic with GP01 module. 

 

 RS 232 or 485 digital outputs: BR 2 A, terminals 1 to 6. 

- Cable PC-DB9 uses RS 232 with Tx on 2, Rx on 3 and 0 Volt on 5. 

For a permanent link (logic controller, modem … ) : 
.  For RS 485: connect Rx 

– to terminal 3 and Tx + to terminal 4 

.  For RS 232: connect Tx to terminal 1 and Rx to terminal 2 with common to 5 . 
. No need of any other connection to validate RS 232.  
. Connect terminals 5 to 6 to validate RS 485.  

 

- On/Off outputs - Relays (Static): BR 2B, terminals 7 to 10 

– multi-pair cables 

- Comply with the limits V < 100 V; I < 0.1 A; R 

ON 

= 10 Ohm. 

- Each relay Re 1 (terminals 7 & 8) or Re 2 (terminals 9 & 10) will transmit the chosen 

status information in the “General Parameters” menu. 

 

 4 

– 20 mA analog outputs: BR 2B, terminals 11 to 14 – Multi-pair cables. 

- These are independent outputs 

galvanically insulated

 in respect to each other, but 

also with respect to the other MiniSonic circuits and by default are 

passive

 and need 

to  be  connected  to  a  receiver  supplying  the  power  (30  V  max.)  to  allow  a  load  of 
more than 1 k ohm. 

- Output No. 1 (terminals 11 & 12) and output No. 2 (13 & 14) will transmit magnitudes 

and ranges of variation as chosen in the “General Settings” menu: flow rate but also 
speed of sound, gain, etc.… 
- It is possible to carry out internal wiring to allow 

active

 outputs by associating the 

terminal block BR 5 (see diagram) already linked to power supply voltage connected 
to BR1, but with the drawback of losing part of the galvanic insulation. 

 

! With a 12 

V DC or AC supply, R “loop” is limited to 150 or 200 Ohms. 

Attention! If this R loop is too high for the supply, the curent fall down to 4 mA 

 

 Connection to probes: BR 4 (chord 1) & BR 3 (chord 2). 

- Use Twin-ax cables specified by Ultraflux (ET1217 & ET1217A). 

In the industrial version, shield and conductors are separated in the “Y” compartment 

of the Y gland, while leaving a free length of 10 cm to terminal blocks. 

- In the Ex d version, the shields are stopped and connected in the stuffing boxes and 

the conductors will be approximately 15 cm long up to the terminal blocks. 

 

Summary of Contents for Minisonic_600-2

Page 1: ...ual chord Minisonic_600 2 Minisonic 2000 dual chord Minisonic_2000 2 B timent TEXAS ragny Parc 9 All e Rosa Luxemburg 95610 RAGNY FRANCE T l 33 0 1 30 27 27 30 Fax 33 0 1 30 39 84 34 www ultraflux net...

Page 2: ...0 B and 2000 B for dual pipe flow measurement configurations Speed 1 or 2 is for open channel flow velocity measurements This manual is specifically concerned with an element from the family and has b...

Page 3: ...ersion Ex d ATEX Version 4 Wiring diagram 5 Converter Assembling Instructions Mechanical installation Electrical wiring 6 Probes installation 7 Setting and commissioning 8 Detailed Menu layout Measure...

Page 4: ...with tapping at an oblique angle and straight ended probes Or with taps perpendicular to the pipe but with bevel end probes Good geometrical control is essential The construction of a measuring spool...

Page 5: ...afety risks N A Only low voltage 60 V Concerning EMC EN 61000 EN 55022 et EN 50204 Concerning tightness IP EN 60529 Concerning ATEX Directive 94 4 CE EN 60079 0 General rules EN 60079 1 Ex d enclosure...

Page 6: ...C T6 IP 67 See also the specific notice NT 219 B Each touch of the keypad has the same function as above The two glands near the front are reserved for probe cables These connections request the use o...

Page 7: ...8 7 6 5 4 3 14 13 12 BR5 2 1 1 100 mm 4 WIRING DIAGRAM FOR MINISONIC 600 2 2000 2 Low voltage supply See also NT 218 if the GP 01 90 230 V AC 24 V DC if installed The internal cables must be kept as s...

Page 8: ...he limits V 100 V I 0 1 A R ON 10 Ohm Each relay Re 1 terminals 7 8 or Re 2 terminals 9 10 will transmit the chosen status information in the General Parameters menu 4 20 mA analog outputs BR 2B termi...

Page 9: ...mulation of gas planes close to vertical 30 will be avoided A horizontal plane is a good choice excepted when the conduit is vertical For intrusive probes adjust the insertion then the alignment or or...

Page 10: ...ettings using the PC software Refer to the manual supplied with the software CD ROM The fields of the main values to be entered are listed below under Heading 8 The software offers extended configurat...

Page 11: ...els 1 2 and also averaged values Physical measurements time of flight T and difference dT channels 1 2 Totalizers Reset possible by simultaneously pressing and Date and time Change by PC Software Hydr...

Page 12: ...t action to take place An operation will be requested allowing a provisional code to be calculated A second press on will provide access to the existing Languages choice field 8 3 Pipe Settings menu A...

Page 13: ...f Coefficient KH or following data to do its calculation If MANUAL entry of coefficient depending on profile Laminar 1 333 or Turbulent 1 02 to1 08 If AUTO entry of parameters Fluid viscosity Pipe rou...

Page 14: ...Otherwise If MANUAL Gain adjustment If AUTO Margin Over amplification compared to critical gain Go If SM choice position of probes depending on geometrical measurements as distance between probes fac...

Page 15: ...gnment If copy of TOT 1 or TOT 2 relay closing time F maxi If Threshold enter value Q Reset to Zero of TOT t1 t2 This function may be prohibited Parameter settings of two outputs 4 20 mA SA 1 SA 2 by...

Page 16: ...actory Settings menu normally reserved to Ultraflux It permits to adjust a coefficient which optimises the compensation with Clamp on probes value 0 6 to1 6 Another parameter named Delta T band permit...

Page 17: ...ment displayed and transmitted meets your expectations Case 2 The measurement operates but may lack accuracy or is unstable Case 3 The measurement is not reliable or the MiniSonic is displaying a Faul...

Page 18: ...Diameter Flow Rate Assembly and Choice of probes is too low to claim any measurement accuracy Is it possible to revise these choices The measurement conditions reveal poor control of transitions from...

Page 19: ...T 4 Echo Alternating signal peak to peak 4 Volt max 0 65 V negative threshold voltage PT 0 0 Volt Ground PT 2 Synchro Trig on Positive edge 0 to 5 Volt PT 1 Selection windows Echo must be inside PT 3...

Page 20: ...NT 208D GB1 20 20 11 APPENDIX Calibration file example with a MiniSonic 2000 2 on a flow spool with wetted probes SM...

Reviews: