History data for Power/Voltage/Ampere
Click <HISTORY DATA> button on Power Data Screen and history data screen
showing past history of Wattage.(see figure-5)
Figure-5 History data
Click <Main Screen> button to switch back to Main Screen.
Note:
If USB stick is inserted on USB port on the HMI display then “SCREEN CAPTURE” button
will appear on various screens.
Click <SCREEN CAPTURE> button to copy screen image to USB Stick.
WARNING
While Load bank is running (with load applied condition) setting Load Dump Switch to ON
(upward) position will cut off all applied load. However, cooling fan will continue to run until
pre-set cooling time is over
.
A recommended 5 minute cool down period of the cooling fan circuit, with no load applied,
should adequately remove any residual heat from the Load Bank and system components.
WARNING
Click <Load Drop> button any time will cut of all applied load. However, cooling fan will
continue to run until pre-set cooling time is over.