Figure-7 Load Profile
3) Enter require Hr., Min, and KW values for each step and click <ACTIVATE> button.
a. Now Load bank will start operating with Hr., Min. and KW values selected for
step#1. This will be indicated by flashing of step 1 entry fields.
b. ACTIVATE button will now change to DEACTIVATE meaning load profile run
of load bank can be deactivated and hence applied load can be disconnected
anytime by click on this button.
c. Click <BACK> button to display main screen.
d. Flashing <LOAD PROFILE> button on main screen indicates that load bank
is operating with activated load profile.
Note: Following buttons / entries on main screen are disabled when load
profile is active,
i. KW SELECT entry
ii. Load Increase button,
iii. Load Decrease button,
iv. LOAD APPLY button,
v. HR. entry,
vi. MIN. entry,
e. Load bank will continue to operate at KW values, Hr and Min selected for
step#1, then after step#2 will be activated and load bank will operate at the
values selected for step#2.This will be indicated by flashing values under that
step.
f. In this way, load bank will continue to operate until the last step is reached.
Then after the entire load will be disconnected. However, cooling fan will
continue to run until pre-set cooling time is over.