Page 21
The network ID must be set to a unique number between 001
and 127. If two stations attempt to share the same network ID,
all stations may operate erratically and the dimmers may not
respond to any station.
Master stations and remote “Entry” stations must be
linked so that the master station responds to the
correct remote station. Once the stations are linked,
each must have a unique network id.
Network Name
Each device should have a unique network name. This helps
when identifying this device from other network devices. The
network name may be up to (8) characters long
Remoting to another Master Station
LCD stations can be used as a “remote” to another LCD station
which is configured as a “master”. Any button press on a remote
LCD station activates the same button press on the master, and,
all LCD messages displayed on the remote are the same as
displayed on the master. A remote station can also be remote to
another remote.
Remote To Setting:
Valid Values:
•
MASTER - not a remote to any master
•
xxx - ID number of the master station to which this
station is a remote
EDIT NETWORK
NAME=D4104
EDIT NETWORK
REMOTE TO=MASTER