STAR eX Diagnostic Tests
iSTAR eX Installation and Configuration Guide
7–9
Table 7-8:
Rotary Switch SW1 Diagnostic Tests for iSTAR eX
Set SW1 to
Performs this Action
Notes
F
Displays general status messages.
ICU fields are Read Only and cannot be changed.
ICU Block on
0
Displays general status messages. Users can Read, Write,
and Update ICU configuration.
ICU Block off
1
Displays most recent card swipe for 1 second
Fast Mode on
2
Displays most recent card swipe for 7 seconds
Slow Mode on
3
Tests and displays information about manual
inputs
for 1
second
Slow Mode Input Test
4
Tests and displays information about manual
inputs
for 2
seconds
Fast Mode Input Test
5
Activates
output
change display tests for manually
activated outputs and displays information for 2 seconds
Slow Mode Output Test
6
Activates and tests
all onboard outputs
and other
outputs
attached to an iSTAR eX through readers and R/8
boards for 1 second
Fast Mode Output test.
LCD does not display
all
info
7
Activates and tests
all onboard outputs only
on an iSTAR
eX, one by one. Test results are indicated by the LED
associated with each output.
Displays results on LED
8
Tests and displays diagnostic information about Ethernet #1
and Ethernet #2 ports.
Ethernet Port and CF Slot
Test
Summary of Contents for iSTAR eX
Page 12: ...Table of Contents xii iSTAR eX Installation and Configuration Guide...
Page 58: ...Backup and Restore 1 38 iSTAR eX Installation and Configuration Guide...
Page 146: ...Starting the ICU 5 12 iSTAR eX Installation and Configuration Guide Figure 5 4 ICU Main Window...
Page 200: ...STAR eX Diagnostic Tests 7 10 iSTAR eX Installation and Configuration Guide...
Page 212: ...A 12 iSTAR eX Installation and Configuration Guide...