ULTRAFEED VAF-4
4-6 OPERATION Manual 0-5332
4.02 Rear Panel Controls and Features
Art # A-12468
Figure 4-4 Rear Panel View
17. ON/ OFF Switch
Press this switch to turn ON or turn OFF the Wirefeeder.
18. Gas Inlet
5/8-18UNF gas inlet for the shield gas.
19. Control Cable Socket
The control cable connects to the power source at this 19-
pin amphenol connector. It contains the signals required to
allow the welding power source and the wire feeder to work
together as a system.
WARNING
The protective earth ground (pin G) of the control cable
is established ONLY when the power source is properly
grounded. See the power source owner’s manual for
proper grounding methods.
20. Welding Cable Connector
This connector allows us to connect the welding cable to the
Wirefeeder. Please make sure that Weld connection is firmly
secured, or connection could overheat and cause damage.
NOTE
It is essential to make a good connection by pushing it
all the way in and turning it to lock it into place.
21. 4A Circuit Breaker
This circuit breaker protects the Wirefeeder from electrical
faults on the 115VAC circuit. In the event of a fault occuring
this circuit breaker will trip (pop out). A short cooling period
must be allowed before an attempt is made to reset it by
pressing it back in. Refer to Section 5.02 for further details.
Keyway
A
M
L
K
U
N
B
C
P
V
T
J
H
S
R
D
E
F
G
Figure 4-5 Pin Identification
Control Cable
Pin
Function
A
Con (Shorted to B
to turn ON Power Source)
B
Contactor- (Shorted to A to
turn ON Power Source)
C
Voltage Feedback (1V
/ 10V OUTPUT)
D
Not Used
E
115 VAC Hot
F
42VAC and 115VAC Neutral
G
Protective Earth Ground
H
Remote Control Maximum
J
Remote Control Wiper Signal
K
Not Used
L
Power Source Common
M
Arc Established (= +15 VDC)
N
Power Source Select Line, N=0V
to Pin L enable the Wirefeeder
P
Not Used
R
Not Used
S
42VAC Hot
T
Not Used
U
Current Feedback (1V/100A)
V
Not Used
Table 4-3 Control Cable Pin Functions
22. 8A Circuit Breaker
This circuit breaker protects the Wirefeeder from electrical
faults on the 42VAC circuit. In the event of a fault occuring
this circuit breaker will trip (pop out). A short cooling period
must be allowed before an attempt is made to reset it by
pressing it back in. Refer to Section 5.02 for further details.