![turck TBPN-L5-4FDI-4FDX Instructions For Use Manual Download Page 77](http://html1.mh-extra.com/html/turck/tbpn-l5-4fdi-4fdx/tbpn-l5-4fdi-4fdx_instructions-for-use-manual_1181730077.webp)
V01.00 | 2020/07
77
14.3
Technical data – safety outputs
Safety outputs
Suitable for inputs according to EN 61131-2,
type 1
Output level in OFF-state
< 5 V
Output level in OFF-state
< 1 mA
Test pulse resistive load, max.
0.5 ms
Test pulse max.
1.25 ms
Interval between 2 test pulses, typical
500 ms
Interval between 2 test pulses, min.
250 ms
Max. output current
2 A (resistive)
Max. total current for device
9 A
Derating curve
∑ I
[A]
[°C]
7
0
-40
40
70
9
0
Max. output current
2 A (DC load)
Derating curve
I
[A]
[°C]
1.5
0
-40
40
70
2
0
The user has to provide an additional overcurrent protection on site.