Using the configuration memory
9.5.1
Storing a configuration
The safety function is automatically stored to the memory stick after a configuration has been
downloaded to the device via Turck Safety Configurator.
NOTE
Non-safety-related configurations as for example the device's PROFINET name, or
the IP address will not be stored on the memory chip.
Storing the configuration during module start
ü
The device is not supplied.
ü
The memory chip is empty.
ü
The device has stored a valid configuration.
Plug the empty memory chip into the device.
Switch-on the power supply.
a
The configuration will be loaded from the device to the memory stick during device start.
Storing the configuration during operation
ü
The device is connected to the Turck Safety Configurator.
ü
The memory chip is plugged from the device start and contains the actual configuration
(identical configuration as in the Turck Safety Configurator).
Load a new or changed configuration into the device via Turck Safety Configurator.
9.5.2
Loading a configuration from the memory chip
ü
Memory chip with valid configuration
Set the rotary coding switches to 900 (F_Reset)
Execute a power cycle.
ð
The device is reset.
Set the rotary coding switch to an address unequal to "9xx".
Plug the memory chip containing a valid configuration onto the device.
Switch-on the power supply.
a
The configuration will be loaded from the memory chip to the device during device start.
9.5.3
Deleting the memory chip (Erase Memory)
The content of the memory chip can either be deleted by using the rotary coding switches or
via the Turck Safety Configurator.
Deleting the configuration via rotary switch setting (901)
Plug the memory chip into device.
Set the rotary coding switches to 901 (Erase Memory).
Execute a power cycle at the device.
a
The content of the memory chip is deleted. The procedure completed as soon as the ERR
LED stops blinking.