![turck TBPN-L5-4FDI-4FDX Instructions For Use Manual Download Page 18](http://html1.mh-extra.com/html/turck/tbpn-l5-4fdi-4fdx/tbpn-l5-4fdi-4fdx_instructions-for-use-manual_1181730018.webp)
Mounting
Grounding the device
18
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
Removing the grounding clip: Disconnect the direct grounding of the fieldbus level
Use a flat screwdriver to slide the grounding clamp forward and remove it.
Mounting the grounding clip: grounding the fieldbus level directly
Place the grounding clamp between the fieldbus connectors by using a screwdriver in
such way that the clamp contacts the metal housing of the connectors.
The shielding of the fieldbus cables is connected to the grounding clip.
Fig. 8: Mounting the grounding clip
Grounding the device – mounting on a mounting plate
For mounting onto a mounting plate: Fix the Device with an M6 metal screw through the
lower mounting hole.
a
The shielding of the M12 flanges for the I/O level is connected to the reference potential
of the installation via the M6 metal screw.
a
With mounted grounding clip: The shielding of the fieldbus is connected to the reference
potential of the installation via the module grounding of the I/O level.