V01.00 | 2020/07
25
Safe inputs with single-channel mechanical contacts
TB…-L…-…
2 FDI (T2)
1 T1
3 n.c.
4 FDI (T1)
5 T2
Inputs can be queried 1-channel.
Connect sensors via two connection
cables and a Y-plug (i.e. Ident-no.:
6634405) to the M12 sockets of the
modules.
NOTE:
Changes to the preset properties of the inputs
directly affect the performance level to be
achieved. For more information, see the online
help of the Turck Safety Configurator.
6.5.2
Outputs
NOTE
Any change in the test pulse interval of the outputs will change the performance
level. The software and the online help of the software contain further information.
Safe output PP-switching
2 n.c.
1 n.c.
3 GND (V1)
4 FDO +
5 n.c.
TB…-L…-…
For PP-switching outputs, connect the
negative pole of the load to the GND-
connector of the respective output
(pin 3).
Another connection of the negative pole
to the GND of the power supply unit is
not permitted.
The wiring has to allow an exclusion of
faults regarding cross connection.
Safe output PM-switching
2 FDO –
1 n.c.
3 n.c.
4 FDO +
5 n.c.
TB…-L…-…
For PM-switching outputs, connect the
negative pole of the load to the M-con-
nector of the respective output (pin 2).