V01.00 | 2019/10
77
Output assembly instances
EtherNet/IP™
Connection
Output assembly
Control word
[byte]
DXP outputs
[byte]
IO-Link out-
puts [byte]
VAUX [byte]
Instance
Size
[8 bit]
Exclusive Owner 104
132
2
2
64
0
IOL 4 IN/4 OUT
150
20
2
2
16
0
IOL 6 IN/6 OUT
151
28
2
2
24
0
IOL 8 IN/8 OUT
152
36
2
2
32
0
Instance 104 – Exclusive Owner
The description of the parameters can be found in chapter “Parameterizing and configur-
ing” [
Word no.
Bit no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Control Word
0x00
-
reserved
DXP outputs
0x01
-
-
-
-
-
-
-
-
DXP7
-
DXP5
-
DXP3
-
DXP1
-
IO-Link – process output data
0x02…
0x11
16 words per port
0x12…
0x21
0x22…
0x31
0x32…
0x42
Instance 150 – 4 bytes IN/4 bytes OUT
The description of the parameters can be found in chapter “Parameterizing and configur-
ing” [
Word no.
Bit no.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Control Word
0x00
-
reserved
DXP outputs
0x01
-
-
-
-
-
-
-
-
DXP7
-
DXP5
-
DXP3
-
DXP1
-
IO-Link process output data
0x02…
0x03
2 words per port
0x04…
0x05
0x06…
0x07
0x08…
0x09