V01.00 | 2019/10
29
8.2
ARGEE/FLC
The ARGEE FLC programming software can be downloaded free of charge from
The Zip archive "SW_ARGEE_Environment_Vx.x.zip" contains the software and the respective
software documentation.
8.3
Commissioning an IO-Link device with IO-Link V1.0
IO-Link devices in accordance with IO-Link specification V1.0 do not support data storage. If an
IO-Link V1.0 device is used, data storage at the IO-Link port must be deactivated.
Set
Data storage mode
at the port to
deactivated, clear
.
Load the parameter changes into the device.
Connect the IO-Link V1.0 device.
a
The LED IOL at the IO-Link port is green, IO-Link communication active.
Fig. 30: Example: Deactivate or respectively delete the data storage mode with the DTM